10  Servicing
377
10
SMGB0077 rev.0 - 01/2013
10.9.10  Removing Heat Exchanger
D A N G E R
TURN OFF all power source switches.
C A U T I O N
• Recover the refrigerant from the unit before the work.  After all the refrigerant is recovered, turn OFF all power source 
switches.
• Makesurethattheunitwillnotbedamaged.Ifhavingdifcultyinperformingtheworkalone,theworkshallbetaken
by two people.
• Takespecialcarenottobeinjuredbytheheatexchangerns.
  
For RPK-(0.8-1.5)FSN(H)3M
1  Remove the power source wiring, the transition wiring and the wiring for the remote control switch.
2  Push the portion indicated by “PUSH” on the underside of the unit to release the catches at the lower part of the unit.
3  Remove the are nuts attached to the rear piping of the heat exchanger to disconnect the pipings.  Then lift the indoor 
unit up and draw it frontward to remove it.
4  Remove the front panel according to the “Removing Front Panel” chapter.
5  Remove the electrical box according to the “Removing Electrical Box” chapter.
6  Remove the drain pan according to the “Removing Drain Pan” chapter.
Rear Piping of 
Heat Exchanger
Connected
Pipings
 Rear Side of Indoor Unit
7  Release 2 catches on the inside of the piping holder at the rear side of the indoor unit and remove the piping holder.
8  Remove 1 screw xing the right  side of the heat exchanger.   Then remove 2 screws xing the left side of  the heat 
exchanger.
Front Side of Indoor Unit  (The gures above show the examples with the piping for heat exchanger removed.)