Detailed parameter description 
Sleep
Run
 
Set frequency curve:
 
Running frequency curve:
 
 
t1 < P01.20, the inverter does not run
 
 
t0=P01.34, sleep delay
Run
  
t2  
t1  
 
t0  
Frequency lower 
limit f0
 
Frequency f
Time t
 
 
 
Coast to 
stop
t1+t2 ≥P01.20, the inverter runs
 
Setting range: 0.0–3600.0s (valid when P.01.19 is 
2)   
This function code sets the automatic running of 
the inverter at next power-on after power down. 
0: Disabled restart 
1: Enable restart, namely the inverter will run 
automatically after the time set by P01.22 elapses 
if the starting conditions are met. 
Waiting time of 
restart after 
power down 
This function code sets the waiting time before 
automatically running at next power-on after 
power down. 
Output frequency 
Running  
Power off 
Power on
 
Running
 
t
t1 t2
t1=P01.22
t2=P01.23
 
Setting range: 0.0–3600.0s (valid when P01.21 is 
1) 
This function code sets the delay of the inverter’s 
wake-up-from-sleep after running command is 
given, the inverter will start to run and output after 
the time set by P01.23 elapses to realize brake 
release. 
Setting range: 0.0–600.0s 
Open-loop 0Hz 
output selection 
0: No voltage output 
1: With voltage output 
2: Output as per DC brake current of stop