S1 series standard inverter
-102-
Function
code
Name
Detailed parameter description
Default
value
Modify
P01.26
Deceleration time
of
emergency-stop
0.060.0s
2.0s
P01.27
Time of starting
section of
deceleration S
curve
0.050.0s
0.1s
P01.28
Time of ending
section of
deceleration S
curve
0.050.0s
0.1s
P01.29
Short-circuit
brake current
When the inverter starts in direct start mode
(P01.00=0), set P01.30 to a non-zero value to
enter short-circuit brake.
During stop, if the running frequency of inverter is
below the starting frequency of brake after stop,
set P01.31 to a non-zero value to enter
short-circuit brake after stop, and then carry out
DC brake in the time set by P01.12 (refer to
P01.09P01.12).
Setting range of P01.29: 0.0150.0% (inverter)
Setting range of P01.30: 0.050.0s
Setting range of P01.31: 0.050.0s
0.0%
P01.30
Hold time of
short-circuit brake
at startup
0.00s
P01.31
Hold time of
short-circuit brake
at stop
0.00s
P02 group Parameters of motor 1
P02.01
Rated power of
asynchronous
motor 1
0.13000.0kW
Depend
on
model
P02.02
Rated frequency
of asynchronous
motor 1
0.01HzP00.03 (Max. output frequency)
50.00Hz
P02.03
Rated speed of
asynchronous
motor 1
136000rpm
Depend
on
model
P02.04
Rated voltage of
asynchronous
motor 1
01200V
Depend
on
model
P02.05
Rated current of
asynchronous
0.86000.0A
Depend
on

Table of Contents