S1 series standard inverter
-130-
Detailed parameter description
Output terminal state of the last fault
Running frequency of the last but one fault
Ramps reference frequency of the last but one fault
Output voltage of the last but one fault
Output current of the last but one fault
Bus voltage of the last but one fault
Max. temperature of the last but one fault
Input terminal state of the last but one fault
Output terminal state of the last but one fault
P08 group Enhanced functions
See P00.11 and P00.12 for detailed definitions.
S1 series inverter defines four groups of
acceleration/deceleration time, which can be
selected by multi-function digital input terminal
(P05 group). The acceleration/deceleration time
of the inverter is the first group by default.
Setting range: 0.0–3600.0s
Running
frequency of
jogging
This function code is used to define the reference
frequency of the inverter during jogging.
Setting range: 0.00Hz–P00.03 (Max. output
frequency)
Acceleration time
of jogging
Jogging acceleration time is the time needed for
the inverter to accelerate from 0Hz to Max. output
frequency (P00.03).
Jogging deceleration time is the time needed from
decelerating from Max. output frequency (P00.03)
to 0Hz.
Deceleration time
of jogging