For parameter configuration
[AE-62] to [AE-73]
Pre-set position
AE-62
Pre-set position
data
When [AA121]≠10 or [AA121]≠03
-268435455 to +268435455(pls)
Other than above.
-1073741823 to +107374182(pls)
・During absolute position control, turning on the input terminal
085[PSET] sets the current position to the value set in [AE-62]
pre-set position data.
The current position monitor [dA-20] is also changed.
For more information, contact your supplier or local Hitachi inverter
sales office.
Positioning operation adjustment
AE-64 Deceleration stop
distance calculation gain
AE-65 Deceleration stop
distance calculation bias
AE-66 Speed Limit in APR
control
*APR: Automatic Position Regulator
・Adjustment of control operation for positioning operation.
For more information, contact your supplier or local Hitachi inverter
sales office.
Homing (Return to reference position)
AE-70
Homing function selection
00(Low-speed)/
01(High-Speed 1)/
02(High-Speed 2)
AE-71
Direction of homing function
AE-72 Low-speed of homing
function
AE-73 High-Speed of homing
function
*1) The actual setting range is limited to the maximum frequency setting
([Hb105/205] [Hd105/205]).
・Set the Homing function for absolute position mode.
・When using the homeing function, assign the input terminal
080[ORL] Limit signal of homing function and 081[ORG] Start
signal of homing function.
For more information, contact your supplier or local Hitachi inverter
sales office.
[AF101] to [AF109]
DC braking (DB) function
AF101 DC braking
selection, 1st-motor
00(Disable)/01(Enable)/
02(Frequency reference)
AF102 Braking type
selection, 1st-motor
00(DC braking)/
01(Speed servo-lock)/
02(Position servo-lock)
AF103 DC braking
frequency, 1st-motor
AF104 DC braking delay
time, 1st-motor
AF105 DC braking force
setting, 1st-motor *2)
AF106 DC braking active
time at stop, 1st-motor
AF107 DC braking
operation method selection ,
1st-motor
AF108 DC braking force at
start, 1st-motor *2)
AF109 DC braking active
time at start, 1st-motor
・DB function can be activated at start-up and stop state
([AF101]=01) or at setting frequency ([AF101]=02), selectively.
・DC braking can be also used if Intelligent input terminal
030[DB] is ON.
*2) Depending on the setting of Load type selection [Ub-03] and
inverter capacity, an internal limit is applied to DC braking
force.
・Stop DB example (Braking force adjusted by [AF105])
・Start DB example (Braking force adjusted by [AF108])
・Frequency reference DB example (Braking force adjusted
by [AF105])
・When the DC braking time is set as 0.00(s), DC braking is
not operational.