4-22
Chapter 4
For parameter configuration
[AJ-01] to [AJ-10]
PID2 function
Code/Name
Range (unit)
Initial
value
AJ-01 PID2
enable
00(Disable)/01(Enable)/
02(Enable (with inverted output))
00
The PID2 function is enabled with the above parameter.
If [AJ-01]=01 when the PID output reaches a negative
value, the PID output is limited to 0.
If [AJ-01]=02 when the PID output reaches a negative
value, the PID output lets out an inverted output.
By turning on the input terminal 043[PID2], the PID2
output becomes 0.
Code/Name
Range (unit)
Initial value
AJ-02 PID2 deviation inversion
00(Disable)/
01(Enable)
00
PID2 deviation can be reversed.
Code/Name
Range (unit)
Initial
value
AJ-03 PID2 unit selection
Refer <unit table> of
the end of this
chapter.
01
AJ-04 PID2 scale adjustment
(0%)
-10000 to 10000
0
AJ-05 PID2 scale adjustment
(100%)
-10000 to 10000
10000
AJ-06 PID2 scale adjustment
(decimal point position)
0 to 4
2
The unit and display data related to the output of the
PID control can be changed.
Code/Name
Range (unit)
Initial
value
AJ-07 PID2 set-point input
source selection
00 to 13, 15 *2)
07
AJ-10 PID2 set-point setting
-100.00 to 100.00(%)
*1)
0.00
*1) Range will depend on the parameters [AJ-04] [AJ-05] [AJ-06]
When PID2 target value input is selected, if the selected
is the parameter setting, [AJ-10] is enabled.
Code/Name
Range (unit)
Initial
value
AJ-12 PID2 feedback input
source selection
00 to 06/08 to 13 *2)
02
Selects the PID2 feedback reference.
*2) 00(Not used)/01(Terminal[Ai1])/02(Terminal[Ai2])/03(Terminal[Ai3])/
04(Terminal[Ai4])/05(Terminal[Ai5])/06(Terminal[Ai6])/
07(Parameter setting)/08(RS485)/09(Option-1)/10(Option-2)/
11(Option-3)/12(Pulse train input (internal)/
13(Pulse train input (option)/15(PID1 output)
[AJ-13] to [AJ-19]
Code/Name
Range (unit)
Initial
value
AJ-13 PID2 proportional gain
0.0 to 100.0
1.0
AJ-14 PID2 integral time constant
0.0 to 3600.0(s)
1.0
AJ-15 PID2 derivative gain
0.00 to
100.00(s)
0.00
The PID2 gains are set by the above parameters.
If input terminal 044[PIDC2] is active (ON), the value of
the integral constant is cleared. If it is done while the
inverter is in running, the driving condition may
become unstable.
Code/Name
Range (unit)
Initial value
AJ-16 PID2 output range
0.00 to 100.00(%)
0.00
[AJ-16] Limits the output range of the PID. If [AJ-16]
=0.00 the limit is disabled.
Code/Name
Range (unit)
Initial value
AJ-17
PID2 over deviation level
0.00 to 100.00(%)
3.00
When the PID deviation pass over ±[AJ-17], the output
terminal 047[OD2] is activated.
Code/Name
Range (unit)
Initial
value
AJ-18 Turn-off level for the PID2
feedback compare signal
0.00 to 100.00(%)
100.00
AJ-19 Turn-on level for the PID2
feedback compare signal
0.00 to 100.00(%)
0.00
When the PID feedback cross over the [AJ-18] level, the
output terminal function 048[FBV2] is deactivated (OFF).
If it crosses under the [AJ-19] level, is activated (ON).
PID feedback (%)
Time(s)
0%
[AJ-18]
048[FBV2]
RUN command
[AJ-19]
ONON
ON
ON
ONON
PID deviation (%)
Time(s)
0%
[AJ-17]
Output
terminal
047[OD2]
ON
ON
[AJ-17]
PID output (%)
Time(s)
PID
Target
value
[AJ-16]
PID output range
[AJ-16]
]
PID2
deviation
inversion
[AJ-02]
PID
deviation
PID target
value
Feedback
value
+
00
01
-
×(-1)