For parameter configuration
[AJ-01] to [AJ-10]
PID2 function
00(Disable)/01(Enable)/
02(Enable (with inverted output))
・The PID2 function is enabled with the above parameter.
・If [AJ-01]=01 when the PID output reaches a negative
value, the PID output is limited to 0.
・If [AJ-01]=02 when the PID output reaches a negative
value, the PID output lets out an inverted output.
・By turning on the input terminal 043[PID2], the PID2
output becomes 0.
AJ-02 PID2 deviation inversion
・PID2 deviation can be reversed.
AJ-03 PID2 unit selection
Refer <unit table> of
the end of this
chapter.
AJ-04 PID2 scale adjustment
(0%)
AJ-05 PID2 scale adjustment
(100%)
AJ-06 PID2 scale adjustment
(decimal point position)
・The unit and display data related to the output of the
PID control can be changed.
AJ-07 PID2 set-point input
source selection
AJ-10 PID2 set-point setting
*1) Range will depend on the parameters [AJ-04] [AJ-05] [AJ-06]
・When PID2 target value input is selected, if the selected
is the parameter setting, [AJ-10] is enabled.
AJ-12 PID2 feedback input
source selection
・Selects the PID2 feedback reference.
*2) 00(Not used)/01(Terminal[Ai1])/02(Terminal[Ai2])/03(Terminal[Ai3])/
04(Terminal[Ai4])/05(Terminal[Ai5])/06(Terminal[Ai6])/
07(Parameter setting)/08(RS485)/09(Option-1)/10(Option-2)/
11(Option-3)/12(Pulse train input (internal)/
13(Pulse train input (option)/15(PID1 output)
[AJ-13] to [AJ-19]
AJ-13 PID2 proportional gain
AJ-14 PID2 integral time constant
AJ-15 PID2 derivative gain
・The PID2 gains are set by the above parameters.
・If input terminal 044[PIDC2] is active (ON), the value of
the integral constant is cleared. If it is done while the
inverter is in running, the driving condition may
become unstable.
・[AJ-16] Limits the output range of the PID. If [AJ-16]
=0.00 the limit is disabled.
AJ-17
PID2 over deviation level
・When the PID deviation pass over ±[AJ-17], the output
terminal 047[OD2] is activated.
AJ-18 Turn-off level for the PID2
feedback compare signal
AJ-19 Turn-on level for the PID2
feedback compare signal
・When the PID feedback cross over the [AJ-18] level, the
output terminal function 048[FBV2] is deactivated (OFF).
If it crosses under the [AJ-19] level, is activated (ON).
PID2
deviation
inversion
[AJ-02]