4-38
Chapter 4
For parameter configuration
[CC-40] to [CC-60]
Logic output terminals setting
Code/Name
Range (unit)
Initial value
CC-40 LOG1 operand-1
selection
<Intelligent output
terminal function list>
reference *1)
000
CC-41 LOG1 operand-2
selection
<Intelligent output
terminal function list>
reference *1)
000
CC-42 LOG1 logical
calculation selection
00(AND)/01(OR)/
02(XOR)
00
CC-43 LOG2 operand-1
selection
<Intelligent output
terminal function list>
reference *1)
000
CC-44 LOG2 operand-2
selection
<Intelligent output
terminal function list>
reference *1)
000
CC-45 LOG2 logical
calculation selection
00(AND)/01(OR)/
02(XOR)
00
CC-46 LOG3 operand-1
selection
<Intelligent output
terminal function list>
reference *1)
000
CC-47 LOG3 operand-2
selection
<Intelligent output
terminal function list>
reference *1)
000
CC-48 LOG3 logical
calculation selection
00(AND)/01(OR)/
02(XOR)
00
CC-49 LOG4 operand-1
selection
<Intelligent output
terminal function list>
reference *1)
000
CC-50 LOG4 operand-2
selection
<Intelligent output
terminal function list>
reference *1)
000
CC-51 LOG4 logical
calculation selection
00(AND)/01(OR)/
02(XOR)
00
CC-52 LOG5 operand-1
selection
<Intelligent output
terminal function list>
reference *1)
000
CC-53 LOG5 operand-2
selection
<Intelligent output
terminal function list>
reference *1)
000
CC-54 LOG5 logical
calculation selection
00(AND)/01(OR)/
02(XOR)
00
CC-55 LOG6 operand-1
selection
<Intelligent output
terminal function list>
reference *1)
000
CC-56 LOG6 operand-2
selection
<Intelligent output
terminal function list>
reference *1)
000
CC-57 LOG6 logical
calculation selection
00(AND)/01(OR)/
02(XOR)
00
CC-58 LOG7 operand-1
selection
<Intelligent output
terminal function list>
reference *1)
000
CC-59 LOG7 operand-2
selection
<Intelligent output
terminal function list>
reference *1)
000
CC-60 LOG7 logical
calculation selection
00(AND)/01(OR)/
02(XOR)
00
*1) 062[LOG1] to 068[LOG7] can not be selected.
The logical operation function outputs the operation
results of the two selected output functions to the
output terminal functions [LOG1] to [LOG7].
[Cd-01] to [Cd-35]
Analog output terminal adjustment
Code/Name
Range (unit)
Initial
value
Cd-01 [FM] Output wave form
selection
00(PWM)/
01(Frequency)
00
Cd-02 [FM] Output base
frequency (At digital frequency
output)
0 to 3600(Hz)
2880
Cd-03 [FM] Output monitor
selection
(Select from d*-*,
F*-*
parameters)
dA-01
Cd-04 [Ao1] Output monitor
selection
dA-01
Cd-05 [Ao2] Output monitor
selection
dA-01
Cd-10 Analog monitor
adjustment mode enable
00(Disable)/
01(Enable)
00
Cd-11 [FM] Output filter time
constant
1 to 500(ms)
100
Cd-12 [FM] Data type
selection
00(Absolute value)/
01(Signed value)
00
Cd-13 [FM] Bias adjustment
-100.0 to 100.0(%)
0.0
Cd-14 [FM] Gain adjustment
-1000.0 to
1000.0(%)
100.0
Cd-15 Adjustment mode [FM]
output level
-100.0 to 100.0(%)
100.0
Cd-21 [Ao1] Output filter time
constant
1 to 500(ms)
100
Cd-22 [Ao1] Data type
selection
00(Absolute value)/
01(Signed value)
00
Cd-23 [Ao1] Bias adjustment
-100.0 to 100.0(%)
0.0
Cd-24 [Ao1] Gain adjustment
-1000.0 to
1000.0(%)
100.0
Cd-25 Adjustment mode [Ao1]
output level
-100.0 to 100.0(%)
100.0
Cd-31 [Ao2] Output filter time
constant
1 to 500(ms)
100
Cd-32 [Ao2] Data type se
lection
00(Absolute value)/
01(Signed value)
00
Cd-33 [Ao2] Bias adjustment
-100.0 to 100.0(%)
20.0
Cd-34 [Ao2] Gain adjustment
-1000.0 to
1000.0(%)
80.0
*2)
Cd-35 Adjustment mode [Ao2]
output level
-100.0 to 100.0(%)
100.0
*2) In Ver2.01 and older, inirtial value is 100.0%
Regarding the adjustment method of the Analog output,
refer to chapter 3.

Related product manuals