For parameter configuration
[CE101] to [CE107]
Low-current detection signal
CE101 Low current
signal output mode
selection, 1st motor
00(During Accel/Decel and
constant speed)
01(During constant speed
only)
CE102
Low current detection
level 1, 1st motor
Inverter rated
current×(0.00 to 2.00)(A)
Inverter
rated current
×1.00(A)
CE103
Low current detection
level 2, 1st motor
Inverter rated
current×(0.00 to 2.00)(A)
Inverter
rated current
×1.00(A)
・When the output current is lower than the set value, output
terminal 033[LOC]/034[LOC2] Low-current indication signal
1/2 Outputs low current signal.
Overload detection signal
CE105
Overload signal output
mode selection, 1st
motor
00(During Accel/Decel
and constant speed)/
01(During constant
speed only)
CE106 Overload
warning level 1, 1st
motor
Inverter rated
current×(0.00 to 2.00)(A)
Inverter
rated current
×1.00(A)
CE107 Overload
warning level 2, 1st
motor
Inverter rated
current×(0.00 to 2.00)(A)
Inverter
rated current
×1.00(A)
・When overload occurs, Output terminal
035[OL]/036[OL2] overload notice advance signals are
output.
[CE-10] to [CE-31]
Frequency arrival signal
CE-10 Arrival frequency 1 value setting
during acceleration
CE-11 Arrival frequency 1 value setting
during deceleration
CE-12 Arrival frequency 2 value setting
during acceleration
CE-13 Arrival frequency 2 value setting
during deceleration
・Above parameters set the operation of the frequency
arrival signal.
(Example) In 003[FA2]/005[FA4] case:
(Example) In 004[FA3]/006[FA5] case:
Over-torque signal
CE120 Over-torque level (Forward
drive), 1st motor
CE121 Over-torque level (Reverse
regenerative), 1st motor
CE122 Over-torque level (Reverse
drive), 1st motor
CE123 Over-torque level (Forward
regenerative), 1st motor
・Sets the level to output the 019[OTQ] signal, when using
vector control and the torque goes over the limit.
Electronic thermal warning
CE-30 Electronic thermal warning level
(MTR)
CE-31 Electronic thermal warning level
(CTL)
・[CE-30] sets the level to output the motor electronic
thermal warning 026[THM].
・[CE-31] sets the level to output the inverter electronic
thermal warning 027[THC].
fon:Maximum frequency 1%
foff:Maximum frequency 2%
fon:Maximum frequency 1%
foff:Maximum frequency 2%
Overload warning
level [CE106]/[CE107]
Low-current
indication signal
detection level
[CE102]/[CE103]
[LOC]/[LOC2]
indication signal