For parameter configuration
[CE-33] to [CE-51]
0Hz speed detection signal
CE-33 Zero speed detection level
・Set the level in which the output terminal 040[ZS] Zero
speed detection turns ON.
Cooling fin overheat warning signal
CE-34 Cooling fin overheat
warning level
・Set the level in which output terminal 032[OHF]Heat
sink overheat warning turns ON.
Accumulated RUN time /
Accumulated PowerON time warning
CE-36 Accum. RUN time (RNT) /
Accum. Power-On time (ONT) setting
・Set the warning level in which the output terminal
024[RNT] accumulated operation time over and output
terminal 025[ONT] accumulated power-on time over
turn ON.
Window comparator (detection of terminal
disconnection)
CE-40 [Ai1] Window
comparator higher limit
CE-41 [Ai1] Window
comparator lower limit
CE-42 [Ai1] Window
comparator hysteresis width
CE-43 [Ai2] Window
comparator higher limit
CE-44 [Ai2] Window
comparator lower limit
CE-45 [Ai2] Window
comparator hysteresis width
CE-46 [Ai3] Window
comparator higher limit
CE-47 [Ai3] Window
comparator lower limit
CE-48 [Ai3] Window
comparator hysteresis width
CE-50 [Ai1] Operation set level
at disconnection or compare
event
CE-51 [Ai1] Operation set level
implement timing
00(Disable)/
01(Enable(at
WC*active)/
02(Enable(at
WC*de-active)
[CE-52] to [CE-55][CE201]to[CE223]
CE-52 [Ai2] Operation set level
at disconnection or compare
event
CE-53 [Ai2] Operation set level
implement timing
00(Disable)/
01(Enable
(at WC*active)/
02(Enable
(at WC*de-active)
CE-54 [Ai3] Operation set level
at disconnection or compare
event
CE-55 [Ai3] Operation set level
implement timing
00(Disable)/
01(Enable
(at WC*active)/
02(Enable
(at WC*de-active)
・Window comparator function output signals whenever the
analog inputs value are within or out of range.
・In the case of disconnection judgment, the reference value
can be set to the [CE-50]/[CE-52]/[CE-54] setting value
when it is within or out of the range of the window
comparator.
If in case [CE-51] [CE-53] [CE-55] = 02:
2nd motor When Intelligent Input terminal 024[SET] is enabled.
CE201 Low current signal output mode
selection, 2nd-motor
CE202 Low current detection level 1,
2nd-motor
CE203 Low current detection level 2,
2nd-motor
CE205 Overcurrent signal output mode
selection, 2nd-motor
CE206 Overcurrent detection level 1,
2nd-motor
CE207 Overcurrent detection level 2,
2nd-motor
CE220 Over-torque level (Forward
drive), 2nd-motor
CE221 Over-torque level (Reverse
regenerative), 2nd-motor
CE222 Over-torque level (Reverse
drive), 2nd-motor
CE223 Over-torque level (Forward
regenerative), 2nd motor
Min
(Ai1/Ai2:0%)
(Ai3:-100%)
Analog operation level
at disconnection
CE-50/CE-52/CE-54
Maximum-limit level
of window comparator
CE-40/CE-43/CE-46
Minimum-limit level of
window comparator
CE-41/CF-44/CF-47
Hysteresis width
[CE-42]/[CE-45]/[CE-48]