For parameter configuration
[UA-90]to[UA-94][Ub-01]to[Ub-05]
[UC-01]
MOP keypad setting
UA-90
Waiting time for turning off
the display(MOP)
UA-91
Initial display selection
(MOP)
(Select from d----,
F---- parameters)
UA-92
Enable auto-return to the
initial display (MOP)
UA-93
Enable frequency changes
through monitor
display(MOP)
UA-94
Enable multi-speed
frequency changes through
monitor display (MOP)
・Above parameters set the behavior of the MOP keypad.
Initialize
Ub-01 Initialize
mode selection
00(Disable)/
01(Error history clear)/
02(Data initialize)/
03(Error history clear & Data
initialize)/
04(Error history clear & Data
initialize & EzSQ clear)/
05(All data except terminal
configuration)/
06(All data except
communication
configuration)
07(All data except terminal &
communication
configuration)/
08(EzSQ only)
Ub-02 Initialize
data selection
00(JP)/01(EU)/
02(US)/03(CHN)
00(JPN)
01(EU)
02(USA)
03(CHN)
Ub-03
Load type selection
00(Very Low Duty)/
01(Low Duty)/
02(Normal Duty)
Ub-05 Enable
initialization
00(Disable)/
01(Execute initialization)
・How to initialize; at first select the initial mode at [Ub-01], next,
when [Ub-05] is set to 1, initialize process is start.
・Once setting the load type selection [Ub-03], the inverter load
rating will be changed instantaneously.
・SH1-03410-H(SH1-1600H) ~ SH1-04810-H(SH1-2200H) support
only normal duty(ND) and low duty (LD).
Factory setting
[Ud-01] to [Ud-37]
Trace function
Ud-01 Trace function enable
Ud-03 Number of trace data setting
Ud-04 Number of trace signals setting
Ud-10 Trace data 0 selection
(parameters of
the d**** and
F**** mode)
Ud-11 Trace data 1 selection
Ud-12 Trace data 2 selection
Ud-13 Trace data 3 selection
Ud-14 Trace data 4 selection
Ud-15 Trace data 5 selection
Ud-16 Trace data 6 selection
Ud-17 Trace data 7 selection
Ud-20 Trace signal 0 input/output
selection
00(Input:[Ud-21
])/01(Output:
[Ud-22])
Ud-21 Trace signal 0 input terminal
selection
Ud-22 Trace signal 0 output terminal
selection
Ud-23 Trace signal 1 input/output
selection
00(Input:[Ud-24
])/01(Output:
[Ud-25])
Ud-24 Trace signal 1 input terminal
selection
Ud-25 Trace signal 1 output terminal
selection
Ud-26 Trace signal 2 input/output
selection
00(Input:[Ud-27
])/01(Output:
[Ud-28])
Ud-27 Trace signal 2 input terminal
selection
Ud-28 Trace signal 2 output terminal
selection
Ud-29 Trace signal 3 input/output
selection
00(Input:[Ud-30
])/01(Output:
[Ud-31])
Ud-30 Trace signal 3 input terminal
selection
Ud-31 Trace signal 3 output terminal
selection
Ud-32 Trace signal 4 input/output
selection
00(Input:[Ud-33
])/01(Output:
[Ud-34])
Ud-33 Trace signal 4 input terminal
selection
Ud-34 Trace signal 4 output terminal
selection
Ud-35 Trace signal 5 input/output
selection
00(Input:[Ud-36
])/01(Output:
[Ud-37])
Ud-36 Trace signal 5 input terminal
selection
Ud-37 Trace signal 5 output terminal
selection
*1) Trace start is also possible from ON of input terminal 108[DTR] or
from ProDriveNext. And while the inverter is in trace function, the
output terminal 079[TRA] turns ON.
For more information, contact your supplier or local Hitachi inverter
sales office.