6-2
Wiring Example
6.4 External device
The all power supply connected to I/O terminal block must
comply with SELV or PELV.
The signal lines to ST1 and ST2 terminals must be physically
separated or appropriately protected.
The all devices used to deliver safety signals must comply
with the function safety norms such as EN ISO 13849-1,
IEC61508.
The configuration of all components used in any circuit
other than an appropriately pre-approved safety module
that interfaces with the Safety function terminals MUST be
at least equivalent to PLe under EN ISO 13849-1 in order to
be able to claim PLe for the combination of SJ-P1/P1-FS and
external circuits.
Example of Safety relay
The width of test pulse (OFF pulse) applied to input
terminals must be 300us or shorter
The followings are the examples of the safety devices to be
combined.
ISO13849-1 cat4, PL e / IEC 61511 SIL 3
EN IEC62061 SIL CL 3
ISO13849-1 cat4, PL e
IEC 61508 SIL 3
PSR-SCP-24DC/ESD/4X1/30
-2981800
ISO13849-1 cat3/4, PL d/e
IEC61508 SIL 3 / IEC62061 SIL CL 3
Compatible standard
Safety Switch
(E.g. Emergency switch)
Physical separation or appropriate cable
protection (e.g. double-shielded cable)