Default Setting
-FE(CE) -FU(UL)
Change
during operation
(allowed or not)
Setting
during operation
(allowed or not)
Integral time setting for nonstop operation at power loss
Maximum-limit level of window comparators O
Minimum-limit level of window comparators O
Hysteresis width of window comparators O
Maximum-limit level of window comparators OI
Minimum-limit level of window comparators OI
Hysteresis width of window comparators OI
Maximum-limit level of window comparators OI
Minimum-limit level of window comparators O/OI/O2
Hysteresis width of window comparators O/OI/O2
Operation level at O disconnection
Operation level at OI disconnection
Operation level at O2 disconnection
Cumulative input power data clearance
Cumulative input power display gain setting
Start frequency adjustment
Carrier frequency setting
Initialization mode (parameters or trip history)
Country code for initialization
Frequency scaling conversion factor
STOP key enable
Restart mode after FRS
Automatic carrier frequency reduction
Dynamic braking usage ratio
Stop mode selection
Cooling fan control
Dynamic braking control
Dynamic braking activation level
Thermistor for thermal protection control
Thermal protection level setting
Free-setting V/f frequency (1)
Free-setting V/f voltage (1)
Free-setting V/f frequency (2)
Free-setting V/f voltage (2)
Free-setting V/f frequency (3)
Free-setting V/f voltage (3)
Free-setting V/f frequency (4)
Free-setting V/f voltage (4)
Free-setting V/f frequency (5)
Free-setting V/f voltage (5)
Free-setting V/f frequency (6)
Free-setting V/f voltage (6)
Free-setting V/f frequency (7)
Free-setting V/f voltage (7)
Brake control enable
Brake wait time for release
Brake wait time for acceleration
Brake wait time for stopping
Brake wait time for confirmation
Brake release frequency setting
Brake release current setting
Braking frequency
Overvoltage suppression enable
Overvoltage suppression level
Acceleration and deceleration rate at overvoltage suppression
Overvoltage suppression propotional gain
Overvoltage suppression Integral time
Window comparatorOthersFree setting of V/f characteristicOthers
Code
Function Name
Monitored data or setting
b056
b060
b061
b062
b063
b064
b065
b066
b067
b068
b070
b071
b072
b078
b079
b082
b083
b084
b085
b086
b087
b088
b089
b090
b091
b092
b095
b096
b098
b099
b100
b101
b102
b103
b104
b105
b106
b107
b108
b109
b110
b111
b112
b113
b120
b121
b122
b123
b124
b125
b126
b127
b130
b131
b132
b133
b134
0.0 to 9.999 /10.00 to 65.55
0. to 100. (lower limit : b061 + b062 / 2) (%)
0. to 100. (lower limit : b060 - b062 / 2) (%)
0. to 10. (lower limit : b061 - b062 / 2) (%)
0. to 100. (lower limit : b064 + b066 / 2) (%)
0. to 100. (lower limit : b063 - b066 / 2) (%)
0. to 10. (lower limit : b063 - b064 / 2) (%)
-100. to 100. (lower limit : b067 + b068 / 2) (%)
-100. to 100. (lower limit : b066 - b068 / 2) (%)
0. to 10. (lower limit : b066 - b067 / 2) (%)
0 to 100 (%) or "no" (ignore)
0 to 100 (%) or "no" (ignore)
0 to 100 (%) or "no" (ignore)
Clearance by setting "01" and pressing the STR key
1. to 1000.
0.10 to 9.99 (Hz)
0.5 to 15.0 (kHz) (subject to derating)
00 (clearing the trip history), 01 (initializing the data), 02 (clearing the trip history and initializing the data)
00 (Japan), 01 (EU), 02 (U.S.A.)
0.1 to 99.0
00 (enabling), 01 (disabling), 02 (disabling only the function to stop)
00 (starting with 0 Hz), 01 (starting with matching frequency), 02 (starting with active matching frequency)
00: invalid, 01: valid
0.0 to 100.0 (%)
00 (deceleration until stop), 01 (free-run stop)
00 (always operating the fan), 01 (operating the fan only during inverter operation
[including 5 minutes after power-on and power-off])
00 (disabling), 01 (enabling [disabling while the motor is topped]), 02 (enabling [enabling also while the motor is topped])
330 to 380, 660 to 760(V)
00 (disabling the thermistor), 01 (enabling the thermistor with PTC), 02 (enabling the thermistor with NTC)
0. to 9999. (
Ω
)
0. to "free-setting V/f frequency (2)" (Hz)
0.0 to 800.0 (V)
0. to "free-setting V/f frequency (3)" (Hz)
0.0 to 800.0 (V)
0. to "free-setting V/f frequency (4)" (Hz)
0.0 to 800.0 (V)
0. to "free-setting V/f frequency (5)" (Hz)
0.0 to 800.0 (V)
0. to "free-setting V/f frequency (6)" (Hz)
0.0 to 800.0 (V)
0. to "free-setting V/f frequency (7)" (Hz)
0.0 to 800.0 (V)
0. to "free-setting V/f frequency (8)" (Hz)
0.0 to 800.0 (V)
00 (disabling), 01 (enabling)
0.00 to 5.00 (s)
0.00 to 5.00 (s)
0.00 to 5.00 (s)
0.00 to 5.00 (s)
0.00 to 99.99, 100.0 to 400.0 (Hz)
0.0 to 2.00 x "rated current"
0.00 to 99.99, 100.0 to 400.0 (Hz)
00 (disabling the restraint), 01 (decelerating and stagnating), 02 (enabling acceleration)
330 to 390 (V) (200 V class model), 660 to 780 (V) (400 V class model)
0.10 to 30.00 (s)
0.00 to 2.55
0.000 to 9.999 / 10.00 to 63.53 (s)
Code
Function Name
Default Setting
-FE(CE) -FU(UL)
Change
during operation
(allowed or not)
Setting
during operation
(allowed or not)
Monitored data or setting
Intelligent input terminals
Code
C GROUP: INTELLIGENT TERMINAL FUNCTIONS
01 (RV: Reverse RUN), 02 (CF1: Multispeed 1 setting), 03 (CF2: Multispeed 2 setting),
04 (CF3: Multispeed 3 setting), 05 (CF4: Multispeed 4 setting), 06 (JG: Jogging), 07 (DB:
external DC braking), 08 (SET: Set 2nd motor data), 09 (2CH: 2-stage
acceleration/deceleration), 11 (FRS: free-run stop), 12 (EXT: external trip), 13 (USP:
unattended start protection), 14: (CS: commercial power source enable), 15 (SFT: software
lock), 16 (AT: analog input voltage/current select), 17 (SET3: 3rd motor control), 18 (RS: reset),
20 (STA: starting by 3-wire input), 21 (STP: stopping by 3-wire input), 22 (F/R: forward/reverse
switching by 3-wire input), 23 (PID: PID disable), 24 (PIDC: PID reset), 26 (CAS: control gain
setting), 27 (UP: remote control UP function), 28 (DWN: remote control DOWN function), 29
(DWN: remote control data clearing), 31 (OPE: forcible operation), 32 (SF1: multispeed bit 1),
33 (SF2: multispeed bit 2), 34 (SF3: multispeed bit 3), 35 (SF4: multispeed bit 4), 36 (SF5:
multispeed bit 5), 37 (SF6: multispeed bit 6), 38 (SF7: multispeed bit 7), 39 (OLR: overload
restriction selection), 40 (TL: torque limit enable), 41 (TRQ1: torque limit selection bit 1), 42
(TRQ2: torque limit selection bit 2), 43 (PPI: P/PI mode selection), 44 (BOK: braking
confirmation), 45 (ORT: orientation), 46 (LAC: LAD cancellation), 47 (PCLR: clearance of
position deviation), 48 (STAT: pulse train position command input enable), 50 (ADD: trigger for
frequency addition [A145]), 51 (F-TM: forcible-terminal operation), 52 (ATR: permission of
torque command input), 53 (KHC: cumulative power clearance), 54 (SON: servo-on), 55 (FOC:
pre-excitation), 56 (MI1: general-purpose input 1), 57 (MI2: general-purpose input 2), 58 (MI3:
general-purpose input 3), 59 (MI4: general-purpose input 4), 60 (MI5: general-purpose input 5),
61 (MI6: general-purpose input 6), 62 (MI7: general-purpose input 7), 63 (MI8: general-purpose
input 8), 65 (AHD: analog command holding), 66 (CP1: multistage position settings selection 1
), 67 (CP2: multistage position settings selection 2), 68 (CP3: multistage position settings
selection 3), 69 (ORL: Zero-return limit function), 70 (ORG: Zero-return trigger function), 71
(FOT: forward drive stop), 72 (ROT: reverse drive stop), 73 (SPD: speed / position switching),
74 (PCNT: pulse counter), 75 (PCC: pulse counter clear), no (NO: no assignment)
[◯
= Allowed
×
= Not permitted
] [◯ ]
[◯
= Allowed
×
= Not permitted
]
Rated current of inverterx 1..0
0.100
100
0
0
100
0
0
100
-100
0
255(no)
255(no)
127(no)
00
1.
0.50
5.0
00
01
1.0
00
00
00
0.0
00
00
00
360/720
00
3000.
0.
0.0
0.
0.0
0.
0.0
0.
0.0
0.
0.0
0.
0.0
0.
0.0
00
0.00
0.00
0.00
0.00
0.00
0.00
00
380/760
1.00
0.50
0.060
0.100
100
0
0
100
0
0
100
-100
0
255(no)
255(no)
127(no)
00
1.
0.50
5.0
00
01
1.0
00
00
00
0.0
00
00
00
360/720
00
3000.
0.
0.0
0.
0.0
0.
0.0
0.
0.0
0.
0.0
0.
0.0
0.
0.0
00
0.00
0.00
0.00
0.00
0.00
0.00
00
380/760
1.00
0.50
0.060
○
○
○
○
○
○
○
○
○
○
×
×
×
○
×
×
×
×
×
○
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
×
○
×
×
×
○
○
○
×
○
○
○
○
○
○
○
×
×
×
×
×
×
×
×
×
×
×
×
×
×
○
○
○
○
○
○
○
○
○
○
○
○
○
Terminal [1] function (*2)
Terminal [2] function
Terminal [3] function (*2)
Terminal [4] function
Terminal [5] function
Terminal [6] function
Terminal [7] function
Terminal [8] function
C001
C002
C003
C004
C005
C006
C007
C008
18(RS)
16(AT)
06(JG)
11(FRS)
09(2CH)
03(CF2)
02(CF1)
01(RV)
18(RS)
16(AT)
06(JG)
11(FRS)
09(2CH)
13(USP)
02(CF1)
01(RV)
×
×
×
×
×
×
×
×
○
○
○
○
○
○
○
○
*2 When the emergency stop function is enabled (SW1 = ON), "18" (RS) and "64" (EMR) are forcibly written to parameters "C001" and "C003",
respectively. (You cannot arbitrarily write "64" to "C001".) If the SW1 signal is turned off and then turned on, "no" (no assignment) is set in parameter "C003".
13