Determining Wire and Fuse Sizes
The maximum motor current in your application determines the recommended wire size.
The following table gives the wire size in AWG. The Power Lines column applies to the
inverter input power, output wires to the motor, the earth ground connection, and any other
components shown in the Basic System Description on page 12. The Signal Lines
column applies to any wire connecting to the two green connectors just inside the front
cover panel.
Motor Output
Inverter Model
Wiring
Applicable
equipment
kW
HP
Power Lines
Signal Lines
Fuse (UL-rated,
class J, 600V ,
Maximum
allowable current)
VT
CT
VT
CT
0.2
0.1
¼
1/8
WJ200-001SF
AWG16 / 1.3mm
2
(75C only)
18 to 28
AWG / 0.14
to 0.75 mm
2
shielded wire
(see Note 4)
10A
0.4
0.2
½
¼
WJ200-002SF
0.55
0.4
¾
½
WJ200-004SF
1.1
0.75
1.5
1
WJ200-007SF
AWG12 / 3.3mm
2
(75C only)
20A
2.2
1.5
3
2
WJ200-015SF
AWG10 / 5.3mm
2
30A
3.0
2.2
4
3
WJ200-022SF
0.2
0.1
¼
1/8
WJ200-001LF
AWG16 / 1.3mm
2
10A
0.4
0.2
½
¼
WJ200-002LF
0.75
0.4
1
½
WJ200-004LF
1.1
0.75
1.5
1
WJ200-007LF
15A
2.2
1.5
3
2
WJ200-015LF
AWG14 / 2.1mm
2
(75C only)
3.0
2.2
4
3
WJ200-022LF
AWG12 / 3.3mm
2
(75C only)
20A
5.5
3.7
7.5
5
WJ200-037LF
AWG10 / 5.3mm
2
(75C only)
30A
7.5
5.5
10
7.5
WJ200-055LF
AWG6 / 13mm
2
(75C only)
60A
11
7.5
15
10
WJ200-075LF
15
11
20
15
WJ200-110LF
AWG4 / 21mm
2
(75C only)
80A
18.5
15
25
20
WJ200-150LF
AWG2 / 34mm
2
(75C only)
80A
0.75
0.4
1
½
WJ200-004HF
AWG16 / 1.3mm
2
10A
1.5
0.75
2
1
WJ200-007HF
2.2
1.5
3
2
WJ200-015HF
3.0
2.2
4
3
WJ200-022HF
AWG14 / 2.1mm
2
4.0
3.0
5
4
WJ200-030HF
15A
5.5
4.0
7.5
5
WJ200-040HF
AWG12 / 3.3mm
2
(75C only)
7.5
5.5
10
7.5
WJ200-055HF
AWG10/ 5.3mm
2
(75C only)
30A
11
7.5
15
10
WJ200-075HF
15
11
20
15
WJ200-110HF
AWG6 / 13mm
2
(75C only)
50A
18.5
15
25
20
WJ200-150HF
AWG6 / 13mm
2
(75C only)
50A
Note 1: Field wiring must be made by a UL-Listed and CSA-certified closed-loop terminal
connector sized for the wire gauge involved. Connector must be fixed by using
the crimping tool specified by the connector manufacturer.
Note 2: Be sure to consider the capacity of the circuit breaker to be used.
Note 3: Be sure to use a larger wire gauge if power line length exceeds 66ft. (20m).
Note 4: Use 18 AWG / 0.75mm
2
wire for the alarm signal wire ([AL0], [AL1], [AL2]
terminals).