5
Wiring UWP
Push down on the tabs to put the wires into the inner
holes of their corresponding termi nals on the UWP (one
wire per terminal) until they are firmly in place. Gently
tug on the wires to verify they are secure. If you need to
release the wires again, push down the terminal tabs on
the sides of the UWP.
This wiring is just an example,
yours may vary.
Wiring terminal designations
S
Input for wired
indoor or outdoor
sensors
L/A
- A
Heat Pump fault input
(C wire required)
S O/B Changeover valve
Y
Compressor
contactor (stage 1)
AUX -
W2
Auxiliary heat relay
Heat relay (stage 2)
Y2
Compressor
contactor (stage 2)
E Emergency Heat relay
G Fan Relay W Heat relay (stage 1)
C
24 VAC common.
For 2 transformer
systems, use
common wire from
cooling transformer.
K
Connect to K on C-wire
adapter**
U
Unused
R
24 VAC power from
heating transformer*
U Rc
24 VAC power from
cooling transformer*
Note: Not all
terminals may be
used, depending
on the system
type that is being
wired. The most
commonly used
terminals are
shaded.
* Terminal can be jumped using Slider Tab. See “Setting Slider Tabs” above.
** The THP9045A1098 C-wire adapter is used on heat/cool systems when you
only have four wires at the thermostat and you need a fifth wire for a common
wire. Use the K terminal in place of the Y and G terminals on conventional or
heat pump systems to provide control of the fan and the compressor through
a single wire—the unused wire then becomes your common wire. See THP9045
instructions for more information.
Set R Slider Tab.
• Use built-in jumper (R Slider Tab) to
differentiate between one or two transformer
systems.
• If there is only one R wire, and it is connected
to the R, Rc, or RH terminal, set the slider to
the up position (1 wire).
• If there is one wire connected to the R
terminal and one wire connected to the Rc
terminal, set the slider to the down position (2
wires).
NOTE: Slider Tabs for U terminals should be left
in place for other thermostat models.
Setting Slider Tabs
R/Rc slider tab
UWP Mounting System