Testing the System
5-23
PROMPT
VALID ENTRIES EXPLANATION
90 TRBL SOUND
0
Trouble Sounding
0= none
1= one beep every minute
2= normal trouble sound (fast
beeps)
[] to continue
Select type of sounding upon trouble conditions on
zones assigned to this zone type.
\\
90 ALARM SOUND
0
Alarm Sounding
0=none
1= keypad sound only
2= steady siren sounding
3= pulsing siren (temporal)
[] to continue
Select type of sounding upon alarm conditions on
zones assigned to this zone type.
90 Dial Delay
0=No, 1=Yes
Dial Delay?
0=no
1=yes
[] to continue
If selected, faults on zones assigned to this zone
type will delay reporting for whatever length of
time that is selected in dial delay (*50).
90 Disp Option
1
Display Options
0 = no display
1 = display only
2 = chime only
3 = chime & disp.
[] to continue
Select whether faults on zones assigned to this
zone type are displayed at the keypad and/or
cause a chime sound.
Alarm ID: 000
Trouble ID: 000
Contact ID Report Codes
000-999 = report code
[] to continue; returns to Enter
configurable zone type number
prompt.
Enter the desired 3-digit Contact ID report codes
for faults and troubles occurring on zones assigned
to this zone type.
IMPORTANT:
Make sure the code does not conflict with
existing, predefined Contact ID report codes.
See the System Communication section for a
list of standard Contact ID codes.
Zone alarm report code (prompt in *56 Zone
Programming) and Trouble report code (*60)
and relevant restore codes (*70, *71) must be
enabled in order for the Configurable Zone Type
codes to be reported.
Programming Installer and User Schedules
The system provides up to 8 schedules, which can be used to control 12 types of system events at pre-
defined times. 4 schedules are intended for use by the end-user, and 4 are reserved for the installer. In
addition, some events are also reserved for the installer only (listed in the “Enter Event” prompt
paragraph below).
NOTES: The master code can only access schedules 01-04 and events 00-08.
System clock must be set before programming schedules.
Programmed schedules do not take effect until the next scheduled “start” time. (e.g., if
programming a schedule time window for 8AM to 5PM, the schedule does not take effect
until 8AM after the schedule has been programmed.)
Start Scheduling mode by entering installer code + [#] + [6] [4] while in normal operating mode.
The following prompts are displayed: