Installation and Operations Guide
|
ACM-VLX/VLX/EXP/AXM
12
© Honeywell. All Rights Reserved. LT-VLXEXPAXMIOG Rev. 01
Figure 8 Communications conne ctions for VLX and EXP
EXP-2200
ASSEMBLED IN USA
EQUIPMENT 5K05
OPEN ENERGY MANAGEMENT
FOR INDOOR USE ONLY
USE COPPER CONDUCTORS ONLY
CLASS 2 CIRCUITS ONLY
24VDC SOURCE - 250mA TOTAL
POWER: MAX LOAD - 20VA
INCLUDING INTERFERENCE THAT MAY CAUSE UNDESIRED OPERATION.
AND (2) THIS DEVICE MUST ACCEPT ANY INTERFERENCE RECEIVED,
(1) THIS DEVICE MAY NOT CAUSE HARMFUL INTERFERENCE,
OPERATION IS SUBJECT TO THE FOLLOWING TWO CONDITIONS:
THIS DEVICE COMPLIES WITH PART 15 OF THE FCC RULES.
STATUS
LBL-EXP2200-A
EXP-1048
ASSEMBLED IN USA
OPEN ENERG MANAGEMENT
EUIPMENT 5K05
H-O-A
H-O-A
H-O-A
H-O-A
H-O-A
H-O-A
H-O-A
H-O-A
H-O-A
H-O-A
H-O-A
H-O-A
BO 0
BO 1
BO 2
BO 3
AO 0
AO 1
AO 2
AO 3
AO 4
AO 5
AO 6
AO 7
POWER:
MAX LOAD - 68VA
NO BOS - 20VA
24VDC SOURCE - 250mA TOTAL
CLASS 2 CIRCUITS ONL
USE COPPER CONDUCTORS ONL
FOR INDOOR USE ONL
THIS DEVICE COMPLIES WITH PART 15 OF THE FCC RULES.
OPERATION IS SUBECT TO THE FOLLOWING TWO CONDITIONS:
(1) THIS DEVICE MA NOT CAUSE HARMFUL INTERFERENCE,
AND (2) THIS DEVICE MUST ACCEPT AN INTERFERENCE RECEIVED,
INCLUDING INTERFERENCE THAT MA CAUSE UNDESIRED OPERATION.
STATUS
LBL-EXP1048-B
LBL-VLX-A
CPU
SS
ROC
DDC
FLASHING NORMAL OPERATION
ON NORMAL / READ
OFF SERVICE REUIRED
ON ROC LOADED / OPERATIONAL
OFF ROC DOWNLOAD REUIRED
FLASHING DDC LOADED / OPERATIONAL
DIAGNOSTICS
POWER
VLX
ASSEMBLED IN USA
OPEN ENERG MANAGEMENT
EUIPMENT 5K05
POWER: MAX LOAD - 20VA
CLASS 2 CIRCUITS ONL
USE COPPER CONDUCTORS ONL
FOR INDOOR USE ONL
THIS DEVICE COMPLIES WITH PART 15 OF THE FCC RULES.
OPERATION IS SUBECT TO THE FOLLOWING TWO CONDITIONS:
(1) THIS DEVICE MA NOT CAUSE HARMFUL INTERFERENCE,
AND (2) THIS DEVICE MUST ACCEPT AN INTERFERENCE RECEIVED,
INCLUDING INTERFERENCE THAT MA CAUSE UNDESIRED OPERATION.
Ethe rne t Cate gory 5 or be tte r drop cable
with RJ-45 jack. Re commended BACne t
network conne ction. Se e page 31.
MS/TP S upports up to 10
BACne t MS /TP de vice s .
Se e page 32.
AC-2650 to conne ct
compute r for
Hype rTe rminal
configuration or te s ting.
Se e page 40 and
page 69.
Pane l g ro und to te rminate s hie lds
and unit ground. S e e page 25.
EXP
communications
c able 18 AWG two
conductor twis ted-
shie ld cable . 18”
(457mm) max.
be twe e n units .
Te rminating
re s is to rs 120 Ohm
matche d pre cis ion
te rminating re s is tors
at each end.
Shie ld Run one e nd to
pane l ground, tape back
at othe r end. Tie through
at inte rme diate EXPs .