EAGLE CONTROLLER – INSTALLATION & COMMISSIONING INSTRUCTIONS
EN1Z-0970GE51 R1112 16
open circuit 3000 (24 VDC on BI terminal)
closed circuit 500 (short-circuit current: 2.0 mA)
The polarity (normal = N.O. contact or reverse = N.C. contact)
configuration defines if a logical 1 or a logical 0 is detected for
a closed contact. This is done by selecting (in CARE) one of
the following options:
normal (default)
closed external contact state=1
open external contact state=0
reverse
closed external contact state=0
open external contact state=1
Pulse Counter Specifications
Using CARE, the binary inputs of the EAGLE can be con-
figured as pulse counters (fast totalizers) for operation in
conjunction with devices equipped with an open collector
output.
If the duty cycle is 50% / 50%, the pulse counter supports up
to 15 Hz. Counting is done on the rising edge.
Table 14. BIs of EAGLE configured as fast totalizers
frequency
max. 15 Hz
pulse ON
min. 25 ms
pulse OFF
min. 25 ms
bounce
max. 5 ms
COM
FAST
TOTALIZER
DRY CONTACT
24 VDC =
0 V =
BI
24V
open
closed
GND
Fig. 26. Internal wiring of BI
Binary Outputs
The EAGLE features eight (CLEA2026Bxx) or four
(CLEA2014Bxx) binary outputs arranged in two blocks
(BO1…4 and BO5..8, respectively).
WARNING
Risk of electric shock or equipment damage!
Low voltage and line voltage must not be wired within
the same block.
In the event of an application stop (e.g., during application
download), the binary outputs assume the safety positions
configured in CARE.
The polarity (normal = N.O. contact or reverse = N.C. contact)
configuration defines if a relay is open or closed, depending
upon whether there is a logical 1 or a logical 0. This is done
by selecting (in CARE) one of the following options:
normal (default)
state=1 relay contact is closed
state=0 relay contact is opened
reverse
state=0 relay contact is closed
state=1 relay contact is opened
Table 15. Relay specifications of the EAGLE
block 1 block 2
BO1…3 BO4 BO5…8
contact volt. AC
5…253 V 5…253 V 5…253 V
contact volt. DC
5…30 V 20…30 V 5…30 V
max. contact cur-
rent AC (resistive)
3 A 10 A 3 A
max. contact cur-
rent AC (induct.)
0.3 A* 10 A 0.3 A*
max. contact cur-
rent AC (induct.)
2 A** 10 A 2 A**
max. contact cur-
rent DC
3 A 7 A 3 A
min. load
100 mA /
5 Vdc
40 mA /
24 Vdc
100 mA /
5 Vdc
* typically 250,000 cycles; ** typically 50,000 cycles
NOTE: The total max. sum load for all binary outputs
(BO1…8) equals 14 A.
NOTE: Binary output 4 supports the switching of high in-
rush currents (e.g., motors, incandescent lights,
etc.). The max. allowed switch current is 80 A for a
duration of max. 20 ms.