EAGLE CONTROLLER – INSTALLATION & COMMISSIONING INSTRUCTIONS
25 EN1Z-0970GE51 R1112
TROUBLESHOOTING
EAGLE Controller Troubleshooting
The following LEDs of the EAGLE Controller can be used for troubleshooting purposes:
Power LED (green)
Status LED (red)
Tx (sending data on the isolated BACnet MS/TP Bus) and Rx (receiving data on the isolated BACnet MS/TP Bus) LEDs
Power LED (green) of EAGLE
Table 21. EAGLE Controller power LED
case power LED meaning remedy
1 ON
Normal operation No action necessary.
2 OFF
Power supply not OK.
Check power supply voltage.
Check wiring.
If problem persists, replace hardware.
Status LED (red) of EAGLE
Table 22. EAGLE Controller status LED
case status LED meaning remedy
1
LED remains
OFF after
power-up
Normal operation. No action necessary.
2
LED remains
ON
continuously
after power-up
– No or invalid firmware, or
– No or corrupt application, or
– License invalid or feature missing, or
– I/O module not found or configuration
mismatch, or
– Communication error, or
– Sensor failure on internal inputs, or
– Hardware error detected, or
– USB memory stick error.
Try powering down and then powering up the
EAGLE Controller.
If problem persists, check and – if necessary –
reload the application.
If problem still persists, replace hardware.
Tx and Rx LEDs
Table 23. EAGLE Controller bus LEDs Tx and Rx
case bus LEDs meaning remedy
1
Both Tx and Rx
are flashing
Normal operation; the isolated BACnet
MS/TP Bus is functioning properly.
No action necessary
2
Both Tx and Rx
are OFF
No communication on the isolated BACnet
MS/TP Bus.
Switch ON communication on the isolated BACnet
MS/TP Bus. L1 should then flash. Further handling
like case 4 (below).
3
Rx is flashing
and Tx is OFF
Communication on the isolated BACnet
MS/TP Bus has been switched OFF, but the
EAGLE is receiving data from other
controllers.
Switch ON communication on the isolated BACnet
MS/TP Bus. If this proves unsuccessful, the
hardware may be defective.
4
Tx is flashing
and Rx is OFF
The EAGLE Controller is attempting to
establish communication on the isolated
BACnet MS/TP Bus, but there is no answer.
The communication rate (Kbaud) on the isolated
BACnet MS/TP Bus has not been correctly set;
other controllers on the bus may have been
incorrectly assigned the same device number; wiring
problem or hardware defect.
Panel Bus I/O Module Troubleshooting
Please refer to CentraLine I/O Modules - Installation & Commissioning Instructions (EN1Z-0973GE51) for more information
about Panel Bus I/O module troubleshooting.