EasyManuals Logo

Honeywell CentraLine CLCM1T User Manual

Honeywell CentraLine CLCM1T
12 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #2 background imageLoading...
Page #2 background image
CLCM1T,2T,4T,5T,6T WALL MODULES INSTALLATION INSTRUCTIONS
MU1Z-0901GE51 R0416B 2
Mounting Procedure
1. Disassemble the cover as shown in Fig. 1.
2. CLCM2T,4T,5T,6T, only: Pull off the setpoint dial.
3. Mount the wall module onto the wall outlet box, or bore
wall holes as specified in Fig. 2 and mount the wall
module with appropriate screws.
4. Connect the wires to the terminal block according to
section “Wiring”.
5. CLCM2T,4T,5T,6T, only: Insert the setpoint dial and turn
it clockwise as far as possible.
6. CLCM2T,4T,5T,6T, only: Make sure that the dial's
position is such that the 30 (°C absolute scale) or the +5
(°C relative scale) points to the right-hand side of the wall
module (see Fig. 3).
Fig. 3. Mounting position of setpoint dial
7. CLCM2T,4T,5T,6T, only: If the dial does not have the
correct position, pull the dial off again and reinsert it with
the correct orientation.
8. Remount the cover as depicted in Fig. 1 and make sure
that the tab on the underside engages.
Wiring
SETPOINT
(CLCM2T, only)
TERMINAL
BLOCK
Fig. 4. CLCM1T,2T mother board
SENSOR
SET PT
BYP/FAN
LED
BYP/RTN
LED/RTN
COM
A B
1: W77xx
2: W7753
3: XL500
1: W77xx
2: W7753
3: XL500
FAN SWITCH
(CLCM5T,6T, only)
BYPASS
BUTTON
OVERRIDE
LED
JUMPERS
TERMINAL
BLOCK
SETPOINT
Fig. 5. CLCM4T,5T,6T mother board
Wiring with PANTHER
NOTE: You should always first connect the wall module and
only then install the PANTHER's software.
Wire the terminal blocks as follows:
1. Strip 5 mm of insulation from the conductor.
2. Insert the wire in the required terminal location and
tighten the screw to complete the termination.
3. Verify wall module wiring with Table 3 or Table 3 and
jumper setting with Fig. 6.
IMPORTANT
Screw-type terminal blocks are designed to accept no
more than one 1.5 mm
2
conductor.
Table 2. CLCM1T,2T terminal connections (PANTHER)
wall module
terminal
function
PANTHER
terminal
1
sensor
See COACH
print-out.
2
setpoint (not internally
connected)
3
common
Table 3. CLCM4T,5T,6T terminal connections (PANTHER)
wall module
terminal
function
PANTHER
terminal
1
common / ground
See COACH
print-out.
2
sensor
3
setpoint
4
bypass / fan
5
LED (reserved for connection
to a 4…20 Vdc, 3.5 mA input)
n.a.
6
bypass / rtn
n.a.
7
LED / rtn
n.a.
When all wiring is complete, re-attach the cover of the wall
module as shown in Fig. 1 and make sure that the tab on the
underside engages.
Jumper Setting with PANTHER
The jumper setting of the CLCM4T,5T,6T with the PANTHER
is shown in Fig. 6.
1: W77xx
2: W7753
3. XL500
1: W77xx
2: W7753
3. XL500
Fig. 6. Jumper setting of CLCM4T,5T,6T (PANTHER)

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell CentraLine CLCM1T and is the answer not in the manual?

Honeywell CentraLine CLCM1T Specifications

General IconGeneral
BrandHoneywell
ModelCentraLine CLCM1T
CategoryControl Unit
LanguageEnglish

Related product manuals