6 Controller CPU and Scanner Module Kit # 51-52-33-126 1/2018
Scanner 2 Overview
One Scanner2 Module is installed in
each I/O Rack of a redundant system.
I/O ports A connects to CPU-A and
I/O Port B connects to CPU-B of the
redundant C75 Controller CPUs.
Maintains communications with both
Lead and Reserve C75 CPU’s to
facilitate failover.
Reads inputs from modules in rack &
writes outputs to modules in rack.
Required for interface to C75
redundant controllers (cannot use
Scanner1 module with C75’s nor can
Safety be used with Non-Safety).
May be replaced under power.
Cannot use with non-redundant
systems.
Scanner 2 Non-Safety Scanner 2 Safety
Scanner 2 Installation Guidelines
The Scanner 2 module may only be inserted into a dedicated slot location in a Remote I/O Rack.
(Figure 4)
Figure 4
Power
Supply
#1
Power
Status
Module
Power
Supply
#2
Dual Port
Scanner
For C75 CPU
Input/Output Modules
8 slot and 12 slot I/O Racks