ENI7003R8 KO65 2013 
SETTING THE OPTIONAL FEATURES 
1.  Post-purge or no post-purge 
 
Post-purge mode
 (default for all DBC2000E 
models): before going to standby after heat 
demand has ended, the DBC2000E performs a 
15s post-purge cycle to ventilate the burner 
chamber, with the blower switched on and the 
firing rate in low position to save energy. 
 
No post-purge mode
 (selectable option): the 
DBC2000E goes to standby with the blower 
switched off immediately after heat demand ends 
and the firing rate goes to low position. 
 
STD model: 
To enable no post-purge, apply line voltage to 
terminal 12 on the wiring base. Practically this 
means that a jumper is placed between terminals 
1 (L) and 12. 
 
ENH/ULT models: 
To enable no-post-purge, make the correct DIP-
switch setting on the front of the DBC2000E. 
SW1 = POSTPURGE select. 
Factory set to post-purge (SW1=off).   
See fig. 4-5 to locate the DIP switches. 
 
2.  Pilot Ignition (PI) or Direct main 
Burner Ignition (DBI) 
 
PI mode
 (default): the main burner is ignited 
indirectly by using an interrupted or intermittent 
pilot flame. After the pilot is ignited and 
stabelized, the DBC2000E goes for a second trial 
of ignition (2
nd
 safety and main stabilization are 
3s) to ignite the main burner. 
 
DBI mode
 (selectable option): the intermittent 
pilot ignition cycle is used to ignite the main 
burner directly via the spark igniter. The second 
trial for ignition has become redundant in this 
mode. In DBI mode the 2
nd
 safety and main 
stabilization times are 0s and DBC2000E goes 
straight into running/modulate after pilot 
stabilization.     
 
 
STD model: 
To enable DBI mode, apply line voltage to 
terminal 22 on the wiring base. Practically this 
means that a jumper is placed between terminals 
1 (L) and 22. 
 
ENH/ULT models: 
To enable DBI mode, make the correct DIP-switch 
setting on the front of the DBC2000E.   
SW2 = DBI/PI select. Factory set to PI (SW2=off). 
See fig. 4-5 to locate the DIP switches. 
 
3.  Valve Proofing System ā VPS   
(ENH/ULT models only
) 
 
Connect a gas pressure switch (such as the 
C6097A2210) to terminal 22 on the wiring base 
(N.O. contact).   
Rule of thumb: adjust the pressure switch to 0.5x 
the inlet pressure.   
 
Table 5: VPS function: 
VPS is not used (default) 
SW4 = on 
SW5 = off 
performed during pre-purge 
cycle, right after the heat 
SW4 = off 
performed right after the heat 
SW4 = on 
performed before and after 
 
Table 6: VPS timing: 
VPS test time   
10s (default) 
 
SW 1: Post-purge use    (default: off = post-purge enabled) 
SW2: DBI/PI select 
  (default: off = PI enabled) 
SW3: VPS use 
  (default: off = disabled) 
SW4: VPS pre-config
  (default: off = disabled) 
SW5: VPS post-config
  (default: off = disabled) 
SW6: VPS test time 
  (default: off = see timing table) 
SW7: VPS test time 
  (default: off = see timing table) 
SW8: Not used  (for future use) 
 
 
 
 
Fig 4-5 Configuration DIP switches (VPS) on the front of the DBC2000E (ENH/ULT only)