Operation 
8/05  DC1010/1020/1030/1040 Product Manual  23 
3.4.5  Alarm Functions and Associated Prompts 
Make sure each alarm is set properly. 
•  See “Configuration 2” Mode (Table 4-2). Set the required Alarm Code in 
prompts “Ald1”, “Ald2”, and “Ald3”.  
Alarm Code: 00 to 19 (Table 4-3 Alarm Function Selections) 
•  See “Configuration 2” Mode (Table 4-2). Define the Alarm timing required 
for prompts “Alt1”, “Alt2”, and “Alt3”. 
Range: 0-99 min, 59 seconds 
0= flickering alarm, 99:59= continual alarm 
Other = Time delay for alarm 
•  See ‘Operation” Mode (Table 3-3). Enter the deviation value or absolute value 
for prompts “Al1”, “Al2”, and “Al3” depending on the Alarm Code selected 
above.  
•  See “Configuration 2” Mode (Table 4-2). Set the hysteresis of alarms in 
prompt “HYSA”.