Configuration 
24  DC1010/1020/1030/1040 Product Manual  8/05 
4 Configuration 
4.1 Introduction 
Configuration is a dedicated operation where you use straightforward keystroke 
sequences to select and establish (configure) pertinent control data best suited for your 
application.  To assist you in the configuration process, there are prompts that appear in 
the upper and lower displays. Refer to Figure 3-1 
4.2 Configuration 1 
To access ‘Configuration 1’ mode, press the ‘SET’ key for 5 seconds while in 
‘Operation’ mode (Section 3.4) 
Table 4-1 Configuration 1 Mode 
Displays 
 Default Value 
Shown 
Parameter  Description 
.
SETSETSETSET
..
SETSETSETSET
 
Main Control (OUT 1) 
P Value (Proportional Band) 
 
 
Proportional - Regulates the controller’s output in 
proportion to the error signal (the difference between 
Process Variable and Setpoint).Range: 0 – 200% 
[For On/Off Control, set P1 = 0. The only other 
prompt required for setting is HYS 1] 
SETSET
 
Main Control (OUT 1) 
I Value (Integral Value) 
 
 
 
Integral - Regulates the controller’s output to the size of 
the error and the time the error has existed. (The 
amount of corrective action depends on the value of 
proportional Gain.) 
Range: 0 – 3200 seconds 
Integral off, I = 0 
SETSET
 
Main Control (OUT 1) 
D Value (Derivative Time) 
 
 
 
Derivative – Regulates the controller’s output in 
proportion to the rate of change of the error. (The 
amount of corrective action depends on the value of 
proportional Gain.) 
Range: 0 – 900 seconds 
Derivative off, D = 0 
SETSET
 
Main Control  
Dead-Band Time 
* DO NOT CHANGE THE VALUE 
SETSET
 
Main Control (OUT 1)  
Auto Tuning Offset 
For Programmer models- 
ATVL means Auto Tuning 
Point. 
Range: 0 – Upper Limit Value (USPL) 
Prevents Overshoot during Autotuning