Programmer (Optional) 
8/05  DC1010/1020/1030/1040 Product Manual  43 
5.4 Program Functions (continued) 
5.4.6  Other Functions  
These other functions [Program Repeat, Power Failure Option, and Program Start from 
PV] are set through the SETS function 
(Refer to Table 4-4 Functions of Sets). 
Table 5-2 Associated Program Functions 
SET  Function  Remarks 
8.1  0 = No Program Repeat 
1 = Program Repeats 
When SET 8.1 = 1, the program will repeat 
from beginning to end.   
8.2  0 = No Power Failure Option 
1 = With Power Failure Option
When SET 8.2 = 1, if power is lost before 
the “target” setpoint is reached, upon power 
recovery, the controller powers up with 
Setpoint = Current PV value and it 
automatically “Restarts” from setpont = 
current PV value up to the original “target” 
setpoint. 
8.3  0 = Program starts from 0 
1 = Program starts from PV 
When SET 8.3 = 1, the setpoint is set to the 
current PV value and the Program then 
starts from this value. The program will be 
more energy efficient, and also decrease 
the time needed to achieve the desired 
setpoint value. The remaining time left to 
reach the setpoint value will be shown in the 
parameter “TIMR” (See Table 5-3 Program 
Configuration Prompts). The time of 
countdown in this instance is related to the 
PV value, not the segment setting.