PCMCIA Option Manual
32
6.6 “PCMCIA PENDING” message is displayed on the recorder
CHECK DIAGNOSTIC / ACTION
Check the PCMCIA STATUS in
PCMCIA / SERVICE :
PCMCIA MISSING
The archive is ON and no card has been inserted in the
driver. Insert
a card to turn off the display.
PCMCIA BAD
The archive is ON and the inserted card is bad. Refer to §
6.
5 to check card validity or insert a valid card.
PCMCIA NOT INIT
The archive is ON and the inserted card is not initialized.
Refer to § 6.4.
PCMCIA PRESENT
The card has been initialized but part of the archiving
config
uration stored on the card does not match with the
configuration of the recorder. Press RESET key and select
RESET PCMCIA menu to make both configurations match.
WARNING Î A RESET
PCMCIA will erase all previous
data stored on the card.
6.7 PCMCIA triangle does not appear on the display when archiving
CHECK DIAGNOSTIC / ACTION
Check INTERFACE parameter in
MISCELLANEOUS / Read
/Write
Turn parameter to PCMCIA.
Check START parameter in
PCMCIA / Read/Write
If the archive is triggered by an alarm or a digital status,
che
ck alarm or digital status which should start the
archiving (Press the DISPLAY key and select ALARM
STATUS or LOGIC STATES).
Is PCMCIA PENDING displayed
on the MMI ?
Refer to § 6.6
6.8 No data have been written on the card
CHECK DIAGNOSTIC / ACTION
Check START parameter in
PCMCIA / Read/Write
The archiving start condition has not been met. No data
have bee
n stored on the card.
Was PCMCIA PENDING displayed
on the MMI ?
Refer to § 6.6
Check ROLLOVER parameter in
PCMCIA / Read/Write
If ROLLOVER is set on DISABLE, check in DIRECTORY
(PCM
CIA / SERVICE) the amount of records that it is still
possible to store. If this amount is 0, no data will be
recorded on this file. Turn ROLLOVER to ENABLE or
either reset or initialize the card.