47
Item Item Name & Description
522 Battery Low Volt Limit
Voltage limit at which the recorder will automatically generate a low voltage alarm if the
battery reading, reads below limit.
Default: 4.30
523 Shutdown Voltage Limit
The voltage level at which “..H.E.L.P..” is displayed on the LCD as an indication that the
battery is about dead and needs to be replaced.
Default: 4.00
528 Clear Alarms
via LCD
This item enables the clearing of all active alarms via the MI Logo. During the Display
List Mode, the "E.E.E.E.E.E.E.E." display will appear after scrolling through all active
alarms. Allow the recorder to time-out (1-minute) at this display to clear the alarms. If
the MI Logo is used to scroll to the next display item in the list the alarms are not
cleared.
Code
0- No
Default: 1-
Yes
530 Display List 1 Item 1 580, Site ID Number
531 Display List 1 Item 2 582, Time
532 Display List 1 Item 3 583, Date
533 Display List 1 Item 4 503, Case Temperature
534 Display List 1 Item 5 521, Battery Voltage Reading
535 Display List 1 Item 6 255, Reserved
536 Live Display Enable
If configured, the recorder will display live P1, P2, and P3 live pressure and temp
erature
readings as part of the Display List. If enabled, the first live parameter will follow the
last Display List 1 item and prior to the first Display List 2 item. All live parameters
have a 30-minute time-out, instead of the usual 1-minute time-out.
Default: Same as item 576
537 Display List 2 Item 1 631, P1 Maximum
538 Display List 2 Item 2 637 Maximum Pressure Time
539 Display Lis
t 2 Item 3 638, Maximum Pressure Date
540 Display List 2 Item 4 632, P1 Minimum
541 Display List 2 Item 5 639, Minimum Pressure Time
542 Display List 2 Item 6 640, Minimum Pressure Date
543 Display List 2 Item 7 651, P1 Interval Low Pressure
544 Display List 2 Item 8 650, P1 Interval High
545 Display List 2 Item 9 649, P1 Interval Average
546 Display List 2 Item 10 255, Re
served
547 Display List 2 Item 11 255, Reserved
548 Display List 2 Item 12 255, Reserved