EasyManua.ls Logo

Honeywell IF-LON2 User Manual

Honeywell IF-LON2
8 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
Page #1 background imageLoading...
Page #1 background image
Copyright © 2017 Honeywell GmbH
All Rights Reserved MU1B-0545GE51 R0117A
IF-LON2
PRODUCT DATA AND MOUNTING INSTRUCTIONS
GENERAL
The Honeywell IF-LON2 LONWORKS® Interface can be used
to connect Honeywell controllers (via their USB port) with
L
ONWORKS ® networks.
BEFORE INSTALLATION
All wiring must comply with local electrical codes and
ordinances or as specified on installation wiring diagrams.
IF-LON2 network wiring can be sized from 1.5 to 0.34 mm
2
,
depending on the application. The maximum length of wire
from the Honeywell controller to the IF-LON2 is 0.5 m.
CAUTION
EMI Noise Introduction. Risk of erratic system
operation.
Keep wiring at least 300 mm away from large induc-
tive loads such as motors, line starters, lighting
ballasts and large power distribution panels. During
installations, try to avoid areas of high EMI noise.
Run IF-LON2 wiring separately from 50 Vac or greater
power wiring.
WARNING / CAUTION
Risk of electric shock or equipment damage!
Disconnect the power supply before making connections
to or removing connections from the IF-LON2’s terminals.
Do not reconnect the power supply until you have com-
pleted the installation.
Observe precautions for handling electrostatic sensitive
devices.
INSTALLATION
The delivery comes complete with the following parts:
IF-LON2 L
ONWORKS
®
Interface;
USB cable (0.5 meter long);
These Product Data and Mounting Instructions (MU1B-
0545GE51).
Software Installation
Beginning with controller firmware version 4.01.00, the
necessary driver software is already installed on the
Honeywell controller.
You can test the proper functioning of the IF-LON2 with your
PC. To do so, proceed as follows:
Download and install OPENLDV 5.00.
Connect the IF-LON2 to your PC's USB port.
Go to "Control Panel" and open "LonWorks interfaces."
RESULT: The IF-LON2 will be displayed as "U60 Network
Interface."
Click on "Wink" and then on "Test." RESULT: "Network
Interface Node Status" will be displayed.
Question and Answer IconNeed help?

Do you have a question about the Honeywell IF-LON2 and is the answer not in the manual?

Honeywell IF-LON2 Specifications

General IconGeneral
BrandHoneywell
ModelIF-LON2
CategoryRecording Equipment
LanguageEnglish

Summary

Safety Warnings and Precautions

Risk of Electric Shock

Disconnect power before making connections to IF-LON2 terminals and complete installation before reconnecting power.

Electrostatic Sensitive Devices

Observe precautions for handling electrostatic sensitive devices to prevent damage.

General Product Information

Before Installation Requirements

Wiring must comply with codes; specify wire sizes (1.5-0.34mm²) and max length (0.5m) for IF-LON2.

EMI Noise Caution

Maintain 300mm distance from inductive loads and power wiring to avoid erratic system operation.

Installation Procedures

Software Installation and Testing

Install drivers for firmware 4.01.00+ and test IF-LON2 function via PC using OPENLDV 5.00.

Hardware and Mounting

Connecting the IF-LON2

Connect IF-LON2 to controller's USB-Client port using supplied USB cable.

DIN Rail Mounting

Mount IF-LON2 onto DIN rail by angling top edge and snapping down until it clicks.

Interface Components

Legend for IF-LON2 connectors (LonWorks, Service LED, LONWORKS LED, Service Pin) and USB.

Technical Specifications

Bus and Network Interfaces

Details on USB Micro-B female, USB 2.0/1.1, and EIA 709-conform TP/FT-10 interfaces.

Environmental and Electrical Specs

Operating temperature, storage temperature, humidity, listings, voltage, and current.

Related product manuals