25
Vigilon Plus fire alarm system
How to use the integral printer 
Assuming the panel has an integral printer:
To Switch On / Off the Printer 
a.  Press the MENU ON/OFF button.
b.  Press the F1 button to select [Control].
c.  Press the F3 button to select [Printer]. Check that ‘Printer’ 
appears on the screen.
d.  Press the F3 button to select [On] / [Off] and then press the 
F2 button to select [Enter]. ‘Printer is on/off’ is displayed. 
To action a Paper Feed
a.  Press the MENU ON/OFF button.
b.  Press the F1 button to select [Control].
c.  Press the F3 button to select [Printer]. Check that ‘Printer’ 
appears on the screen.
d.  Press the F2 button to select [Paper Fd]. Note the display 
and menu prompts are cleared. Printer performs 8 line feeds.
To conduct a Printer Test
a.  Press the MENU ON/OFF button.
b.  Press the F1 button to select [Control].
c.  Press the F3 button to select [Printer]. Check that ‘Printer’ 
appears on the screen.
d.  Press the F1 button to select [Test]. Note the display and 
menu prompts are cleared.
e.  Check that the printer provides a listing of all the characters it 
is capable of printing.
How to enable/disable Sensing
NA
These operations are not applicable for a Vigilon Plus 
Network Node.
  It is only possible to disable a Manual 
Call Point (MCP) individually, not as part 
of a range. DISABLING A MCP IS NOT 
RECOMMENDED.
A sensing device such as a sensor or MCP in the system 
can be disabled/enabled. You will need the device and loop 
numbers, this information can be found in the site specic 
documents held by the person responsible for the re system.
a.  Press the MENU ON/OFF button.
b.  Press the F1 button to select [Control].
c.  Press the F4 button to select [UserCode]. At the ashing 
cursor using and the keypad input your PIN code and then 
press the Enter button.
d.  To disable a device: Press the F2 button to select 
[Disable]. To enable a device: Press the F1 button to 
select [Enable]. The display shows either ‘Enable’ or ‘Disable’.
e.  Press the F1 button to select [Sensing]. Notice ‘Device’ 
followed by a ashing cursor appears on the display. Use 
the keypad to input a device number from a range 1 to 200).
f.  Press the F2 button to select [Loop]. Notice ‘Loop’ 
followed by a ashing cursor on the display. Use the 
keypad to input a loop number from a range 1 to 6.
g.  Press the F2 button to select [Enter]. This is conrmed 
by: ‘Device(s) enabled’ or ‘Device(s) disabled’. The 
Disablement light is lit upon disablement of the device.
www.acornfiresecurity.com
www.acornfiresecurity.com