Honeywell IFP-300 - Check Detector Sensitivity; Set Time and Date; Enable or Disable a Point; View Event History

Honeywell IFP-300
2 pages
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Check Detector
Sensitivity
1.
Press
ENTER
to access Main
Menu.
2.
Press 2 for Point Status.
3.
From the list that displays, select the SLC module where the point you want to view is
located.
4.
The fourth line of the display shows the sensitivity status. “NORMAL” means the
detector is in compliance with NFPA 72.
“CAL MAINT” means the detector is in compliance with NFPA 72 but maintenance should
be performed soon.
“CAL TRBLE” means the detector is not in compliance with NFPA 72.
Set Time and Date
1.
Press
ENTER
to access Main
Menu.
2.
Press 4 to select Set Time & Date. Enter a code if prompted
3.
Make changes in the fields on the screen as necessary.
4.
When the time and date are correct, press ENTER.
Enable / Disable a Point
1.
Press
ENTER
to access Main
Menu.
2.
Press 2 to select Point Functions.
3.
Press 1 for Disable / Enable Pt
4.
Press 7 for Disable / Enable Pt.
5.
Use the Up or Down button to move through the list. Then press ENTER to select the
module where the point you want to disable/enable is located
6.
Enter the point or circuit number that you want to disable/enable.
7.
Press the right arrow key to toggle between NORMAL (enable) or DISABLE.
View Event History
1.
From the Program Menu.
2.
Press 3 to select Event History.
3.
Press the Up or Downbutton to view events in the history buffer.
For Service Call:
(800) 639-2521