EasyManuals Logo

Honeywell IFP-300 User Manual

Honeywell IFP-300
2 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
Page #1 background imageLoading...
Page #1 background image
Model IFP-300 Basic Operating Instructions
These Instructions must be framed and displayed next to the IFP-300 panel in accordance with NFPA 72 fire code for
Local Protected Fire Alarm Systems. Test the system in accordance to NFPA 72.
Operation
Task to Per
form
Silence Alarms and
Troubles
Press
SILENCE
Reset Alarms
Press
RESET
then enter a code if prompted.
View Alarms,
Supervisory, and
Troubles
For each type of condition press the Up or Down button associated for Alarms,
Supervisory, or Troubles.
View status of Point
1.
Press
ENTER
to access Main
Menu.
2.
Press 2 to select Point Functions.
3.
Then press 2 to select Point Status.
4.
Select the module the device is located on by using the Up or Down button. Then
press ENTER.
5.
Enter the point number.
Conduct a Fire Drill
Call service company
May be disabled
May not be allowed by
AHJ in your area.
1.
Press
ENTER
to access Main
Menu.
2.
Then Press 1 to select System Tests.
3.
Press 1 to select Fire Drill.
4.
Press ENTER to start the fire drill.
5.
Press ENTER to end the fire drill.
TROUBLE
FIRE: ALARM SUPERVISORY
CO: ALARM SUPERVISORY
SYSTEM: TROUBLE

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell IFP-300 and is the answer not in the manual?

Honeywell IFP-300 Specifications

General IconGeneral
BrandHoneywell
ModelIFP-300
CategoryControl Panel
LanguageEnglish

Related product manuals