JADE™ ECONOMIZER MODULE
63-2700—05 16
ADVANCED
SETUP
MA LO SET 45ºF 35 to 55 ºF;
increment by 1º
Temp to activate Freeze Protection (close damper and alarm if temp falls
below setup value)
FREEZE POS CLO CLO
MIN
Damper position when freeze protection is active (closed or MIN POS).
CO2 ZERO 0ppm 0 to 500 ppm;
increment by 10
CO2 ppm level to match CO2 sensor start level.
CO2 SPAN 2000ppm 1000 to 3000
ppm;
increment by 50
CO2 ppm span to match CO2 sensor.
STG3 DLY 2.0h 0 min, 5 min, 15
min, then 15
min intervals.
Up to 4h or OFF
Delay after stage 2 for cool has been active. Turns on 2nd stage of cooling
when economizer is 1st stage and mechanical cooling is 2nd stage. Allows
three stages of cooling, 1 economizer and 2 mechanical.
OFF = no Stage 3 cooling.
SD DMPR POS CLO CLO
OPN
Indicates shutdown signal from space thermostat or unitary controller.
When controller receives 24 Vac input on the SD terminal in conventional
mode, the OA damper will open if programmed for OPN and OA damper
will close if programmed for CLO. All other controls, e.g., fans, etc. will
shut off.
DCVCAL ENA MAN MAN (manual)
AUTO
Turns on the DCV automatic control of the dampers. Resets ventilation
based on the RA, OA and MA sensor conditions. See Product Data sheet
63-2700 for details. Requires all 3 RA, OA and MA sensors.
This operation is not operable with a 2-speed fan unit.
MAT T CAL 0.0 F° +/-2.5F° Allows for the operator to adjust for an out of calibration temperature
sensor
OA T CAL 0.0F° +/-2.5F° Allows for the operator to adjust for an out of calibration temperature
sensor
OA H CAL 0% RH +/-10% RH Allows for the operator to adjust for an out of calibration humidity sensor
RA T CAL 0.0F° +/-2.5F° Allows for the operator to adjust for an out of calibration temperature
sensor
RA H CAL 0% RH +/-10% RH Allows for the operator to adjust for an out of calibration humidity sensor
DA T CAL 0.0 F° +/-2.5F° Allows for the operator to adjust for an out of calibration temperature
sensor
2SP FAN DELAY 5 Minutes 0 to 20 minutes
in 1 minute
increments.
When in economizing mode this is the delay for the high speed fan to try to
satisfy the call for second stage cooling before the first stage mechanical
cooling is enabled.
CHECKOUT
f
DAMPER VMIN-
HS
n/a n/a Positions damper to VMIN position
DAMPER VMAX-
HS (LS)
n/a n/a Positions damper to VMAX position. With 2-speed fan units the damper
will position to VMAX low speed fan.
DAMPER OPEN n/a n/a Positions damper to the full open position.
DAMPER CLOSE n/a n/a Positions damper to the fully closed position
CONNECT Y1-O n/a n/a Closes the Y1-O relay (Y1-O)
CONNECT Y2-O n/a n/a Closes the Y2-O relay (Y2-O)
CONNECT EX 1 n/a n/a Closes the power exhaust fan 1 relay (EXH1)
CONNECT
AUX1 O
n/a n/a Energizes the AUX1 O output. The AUX1 O is replaced by:
ERV
EXH2
SYS
Based of AUX1 O switch settings or is not available if AUX1 O is set to
NONE
Table 5. Menu Structure
a
. (Continued)
Menu Parameter
Parameter
Default
Value
Parameter
Range and
Increment
b
Notes