JADE™ ECONOMIZER MODULE
19 63-2700—05
Table 7. Setup and Setpoint Menus.
Menu Parameter
Parameter
Default
Value
Parameter
Range and Increment Notes
SYSTEM SETUP INSTALL 01/01/11 Display order = MM/DD/YY
Setting order = DD, MM, then YY.
UNITS DEG ºF ºF or ºC Sets economizer controller in degrees Fahrenheit or
Celsius.
EQUIPMENT CONV CONV
Heat Pump
CONV = conventional
HP O/B = Enables Heat Pump mode. Use AUX2 I for
Heat Pump input from thermostat or controller.
AUX2 I n/a SD/W or HP(O)/HP(B) In CONV mode:
SD = Enables configuration of shutdown (default);
W = Informs controller that system is in heating
mode.
In HP O/B mode:
HP(O) = energize heat pump on Cool (default);
HP(B) = energize heat pump on Heat.
FAN TYPE 1 speed 1 speed/
2 speed
Sets economizer controller for operation of 1 speed
or 2 speed supply fan
FAN CFM 5000cfm 100 to 15000 cfm;
increment by 100
This is the capacity of the RTU. The value is found
on the label from the RTU manufacturer.
AUX1 OUT NONE NONE
ERV
EXH2
SYS
• NONE = not configured (output is not used)
• ERV= Energy Recovery Ventilator
a
• EXH2 = second damper position relay closure
for second exhaust fan.
• SYS = use output as an alarm signal
OCC INPUT INPUT or ALWAYS When using a setback thermostat with occupancy
out (24 Vac), the 24 Vac is input “INPUT” to the
OCC terminal. If no occupancy output from the
thermostat then change program to “ALWAYS” OR
ad a jumper from terminal R to OCC terminal.
FACTORY DEFAULT NO NO or YES Resets all set points to factory defaults when set to
YES. LCD will briefly flash YES and change to NO
but all parameters will change to factory default
values.