JADE™ ECONOMIZER MODULE
63-2700—05 20
ADVANCED SETUP MA LO SET 45ºF 35 to 55 ºF;
increment by 1º
Temp to activate Freeze Protection (close damper
and alarm if temp falls below setup value)
FREEZE POS CLO CLO
MIN
Damper position when freeze protection is active
(closed or MIN POS).
CO2 ZERO 0ppm 0 to 500 ppm;
increment by 10
CO2 ppm level to match CO2 sensor start level.
CO2 SPAN 2000ppm 1000 to 3000 ppm;
increment by 50
CO2 ppm span to match CO2 sensor.
STG3 DLY 2.0h 0 to 4.0 hours or OFF;
0,5 min,
15 min. then
15 min. increments
up to 4 hours
Delay after stage 2 for cool has been active. Turns
on 2nd stage of cooling when economizer is 1st
stage and mechanical cooling is 2nd stage. Allows
three stages of cooling, 1 economizer and 2
mechanical.
OFF = no Stage 3 cooling.
SD DMPR POS CLO CLO
OPN
Indicates shutdown signal from space thermostat
or unitary controller. When controller receives 24
Vac input on the SD terminal in conventional mode,
the OA damper will open if programmed for OPN
and OA damper will close if programmed for CLO.
All other controls, e.g., fans, etc. will shut off.
DCVCAL ENA MAN MAN (manual)
AUTO
Turns on the DCV automatic control of the
dampers. Resets ventilation based on the RA, OA
and MA sensor conditions. See Product Data sheet
63-2700 for details. Requires all 3 RA, OA and MA
sensors.
This operation is not operable when 2-speed fan
mode enabled.
MAT T CAL 0.0F +/-2.5F Allows for the operator to adjust for an out of
calibration temperature sensor
OA T CAL 0.0F +/-2.5F Allows for the operator to adjust for an out of
calibration temperature sensor
OA H CAL 0% RH +/-10% RH Allows for the operator to adjust for an out of
calibration humidity sensor
RA T CAL 0.0F +/-2.5F Allows for the operator to adjust for an out of
calibration temperature sensor
RA H CAL 0% RH +/-10% Allows for the operator to adjust for an out of
calibration humidity sensor
DA T CAL 0.0F +/-2.5F Allows for the operator to adjust for an out of
calibration temperature sensor
2SP FAN DELAY 5 Minutes 0 to 20 minutes in 1
minute increments.
When in economizing mode this is the delay for the
high speed fan to try to satisfy the call for second
stage cooling before the first stage mechanical
cooling is enabled.
Table 7. Setup and Setpoint Menus. (Continued)
Menu Parameter
Parameter
Default
Value
Parameter
Range and Increment Notes