BCU 440 · Edition 01.17 15
Parameters
4.4 Behaviour during operation
4.4.1 Safety time during operation t
SB
Parameter 14
This indicates the safety time during operation t
SB
for
valve V1.
The default in accordance with EN 298 is 1 s.
The BCU has also the available option of t
SB
of 2 s. Pro-
longing the time increases the installation availability in
the case of brief-duration signal fades (e.g. fades of the
ame signal).
In accordance with EN 7462, the safety time of the
installation during operation (including closing time of
the valves) may not exceed 3 s.
Note the requirements of the Standards!
4.4.2 Fault lock-out or restart
Parameter 12
This parameter determines whether the BCU starts a
one-off restart or performs an immediate fault lock-out
for the burner after an installation fault (flame failure or
failure of air flow).