44 ซ.บรมราชชนนี 70 ถ.บรมราชชนนี ศาลาธรรมสพน์ ทวีวัฒนา กทม. 10170.
website: https://www.add-furnace.com/ โทร: 02-888-3472
Line ID: @add11 e-mail: add028883472@gmail.com
4
.
3
.
3
F
l
am
e
s
im
ul
a
t
io
n
The flame simulation check is conducted after applying
the start-up signal (
) during the waiting time t
W
.
Start-up signal, safety interlock
The start-up signal is the same as the signal in the
safety interlock.
If the start-up/safety interlock signal drops more than
four times in succession during start-up, an inadmissible
quantity of non-combusted gas can reach the combus-
tion chamber during the safety time via open gas valves.
Therefore, a fault lock-out is performed on the automatic
burner control unit IFD 258 following three consecutive
drops of the start-up/safety interlock signal (blinking
).
If flame simulation is signalled during start-up, the flame
simulation delay time t
LV
starts to elapse. If the flame
simulation is discontinued during the flame simulation
delay time t
LV
(max. 25 s), the burner will start up. Oth-
erwise, a fault lock-out occurs. The display blinks and
indicates .
1
L1
3
10
11
5
13–14
8–9
t
W