Lyric Controller Installation and Reference Guide
- 13 -
Wireless Zones
Wireless ZonesWireless Zones
Wireless Zones
General Information
General InformationGeneral Information
General Information
Zones
ZonesZones
Zones
The Lyric Controller supports up to 128 total wireless zones using 5800 and SiX Series transmitters, and wireless
keys.
Range
RangeRange
Range
The built-in RF receiver can detect signals from wireless transmitters within a nominal range of 200 feet.
T
TT
Transmitters
ransmittersransmitters
ransmitters
5800 and SiX Series transmitters have built-in serial numbers that must be entered into the system using the
“Zones” programming section, or input to the controller via AlarmNet 360. Each transmitter's zone number is
also programmed into the system in the “Zones” programming section. Some transmitters, such as the 5816 can
support more than one "zone" (referred to as loops or inputs). On the 5816, for example, the wire connection
terminal block is loop 1; the reed contact is loop 2. Each loop must be assigned a different zone number.
For 5800 Series wireless keys such as the 5804E, 5834-4 and 5878, you must assign a unique zone number to
each individual button used on the transmitter. Each button on the transmitter also has a pre-designated loop
or input number, which is automatically displayed.
Six Series
Six SeriesSix Series
Six Series
Frequency Agility
Frequency AgilityFrequency Agility
Frequency Agility
Communications between the Controller and SiX Series transmitters is automatically monitored by the panel.
When excessive environmental interference (i.e; from Wi-Fi routers) is detected, communications between the
panel and the SiX Series sensors is automatically switched to another quieter channel to allow clearer
communication.
ETL
ETLETL
ETL
The 5816
The 5816 The 5816
The 5816 Transmitt
TransmittTransmitt
Transmitters do n
ers do ners do n
ers do not have EOL
ot have EOL ot have EOL
ot have EOL supervision of their loop wiring
supervision of their loop wiringsupervision of their loop wiring
supervision of their loop wiring, which
, which , which
, which m
mm
must
ustust
ust
not exceed 3 feet.
not exceed 3 feet.not exceed 3 feet.
not exceed 3 feet.
The
The The
The 5800PIR
5800PIR5800PIR
5800PIR-
--
-OD,
OD,OD,
OD,
5800SS1,
5800SS1,5800SS1,
5800SS1,
5804E,
5804E,5804E,
5804E,
5814,
5814, 5814,
5814, 5821, 5877
5821, 58775821, 5877
5821, 5877
and
and and
and 5878
58785878
5878
wireless transmitters
wireless transmitters wireless transmitters
wireless transmitters have not been
have not been have not been
have not been
evaluated by
evaluated by evaluated by
evaluated by ETL
ETLETL
ETL.
..
.
House Identification
House IdentificationHouse Identification
House Identification
If a RF House ID (RF House Code) is required to establish proper communication, the same two-digit code (01–
31) must be programmed in the Lyric, and the device. Refer to the “System Type” programming section in the
Lyric Controller Programming Guide (p/n 800-18077). An RF House ID is not necessary for 5800 Series
transmitters and the entry should be left at “0” (default) in those cases.
Transmitter Supervision
Transmitter SupervisionTransmitter Supervision
Transmitter Supervision
With the exception of some transmitters/keypads that may be carried off-premises (5804E, 5834-4 and
SiXFOB), each transmitter is supervised by a check-in signal that is sent to the receiver at 70–90 minute
intervals. If at least one check-in is not received from each supervised transmitter within a 12-hour period, the
"missing" transmitter zone number(s) and "Supervision" will be displayed. The supervision for a particular
transmitter in the system that may also be carried off the premises may be turned off by entering it as an
“Unsupervised” type. For additional information, refer to the “Zones” programming section in the Lyric
Controller Programming Guide (p/n 800-18077). 5800 and SiX Series transmitters have built-in tamper
protection and will annunciate as a fault condition if covers are removed. In Canada the RF supervision period
is 3-hours for Fire zones and 12 hours for all other zone types.
Transmitter Input Types
Transmitter Input TypesTransmitter Input Types
Transmitter Input Types
Each transmitter has one or more unique factory-assigned input (loop/5800 Series or service/SiX Series) ID
codes. Each of the inputs requires a programming zone (e.g., a 5804E's four inputs require four button zones).
Transmitters can be entered as one of the following types (see transmitter’s instructions for appropriate
Supervision type):
Description
DescriptionDescription
Description
Supervised
in signals, as well as fault, res
tore, and low battery signals. The
transmitter must remain within the receiver's range.
Unsupervised
Sends all the signals that the
check-in signals. The transmitter may therefore be carried off-premises.
Button
o not send low battery signals until
transmitter is unsupervised and may be carried off-premises.