26 Mass Notification — P/N LS10063-000NF-E:E 06/26/2019
Programming Programming
It suppresses fire sequences and pages that come below it in priority, until an MN reset clears the “MN Active Tone”.
Summary of Procedures
Following are the steps involved in creating and programming an MN Active Tone.
1. Build the MN Active Tone Audio Sequence. (See below.)
2. Assign Message Priorities. (See page 27.)
3. Create MN Logic Zones. (See page 28.)
4. Add MN Active Tone Logic to PAM Programming. (See page 28.)
Detailed Procedures
Build the MN Active Tone Audio Sequence
Open the Audio Settings branch of VeriFire Tools DVC programming, and build the MN Active Tone audio sequence on the Message
Sequences tab.
NOTE: Fire or OTHER sequences and pages will not be suppressed for MN alarms without the MN Active Tone, properly prioritized in the
PAM.
Figure 3.14 Creating an MN Active Tone Sequence
1. Select and expand a sequence in the
Message Sequences Number column.
This example uses Sequence 1. Assign
the sequence an Evac message type.
2. Type “MN Active Tone” in the Label
field.
3. Select Command File for “Play
Forever” for Sequence Step 1.
4. Select Wave File for “Active Tone” for
Sequence Step 2.
5. Select Command File for “End Play” for
Sequence Step 3.
6. Press Play Sequence to listen to and
review the sequence as a test. The
Play Forever command will play 200
times as a test, will play forever in a
non-test situation. Use the audio-player
buttons to pause and restart playback.
7. Press Save.

Other manuals for Honeywell Notifier AFP-100