18 Mass Notification — P/N LS10063-000NF-E:E 06/26/2019
Programming Programming
3.3 Programming
3.3.1 DCC Participation
In a system with both MN and Fire, DCC must always be disabled for all NFS-320/SYSs, NFS2-640s, NFS2-3030s, NCA-2s and
ONYXWorks Workstation.
NFS2-3030/NCA-2
Panel: In the Panel Settings Menu, set DCC Participation to NO
to disable DCC Participation.
VeriFire Tools: Leave the Display and Control Center box unchecked in the NFS2-3030 and NCA-2. Do not enable DCC.
NFS2-640/NFS-320/SYS
Panel: In the Utility Program Menu, set “DCC-mode” to “N” (no) to
disable DCC participation.
Figure 3.1 Panel Settings Screen (2), NFS2-3030
PANEL SETTINGS
LCM LOCAL MODE: YES REGIONAL SETTINGS
POWER MANAGEMENT MODE:OFF
DCC PARTICIPATION: NO MORE
RAPID ALL CALL: NO ACCEPT
DEFAULT SETTINGS BACK
Figure 3.2 VeriFire Tools, NFS2-3030/NCA-2
Leave
unchecked.
NCA-2 General Settings Branch, “General
Settings 2” column
NFS2-3030 General Settings Branch, “General
Settings 1” column
Figure 3.3 Utility Program, NFS2-640/NFS-320/SYS
REGION=0 TBL.REMIND=2 ALA.SCROLL=N
LOCAL CONTROL=0 IP-ACCESS=0 DCC-mode:N