38 Mass Notification — P/N LS10063-000NF-E:E 06/26/2019
Operation Mass Notification Events
Flashes the SUPERVISORY yellow LED.
Activates Special Function Zone ZF21 (MN supervisory zone).
Does not suppress Fire or any other activations.
Does not activate “General Supervisory” type ID.
Any device programmed for “Resound by Supervisory” will not resound.
Displays ACTIVE:ECS/MN SUPT or ACTIVE:ECS-MN SUPL in the display, as well as other information specific to the
supervisory message.
Sends an MN Supervisory message to the history buffer and installed printer and annunciators.
Sends an MN supervisory message (ZF21) out to the network.
Network Activation
Logic Zones with ZF21 (MN supervisory zone) will be evaluated.
4.1.3 MN Trouble
MN Trouble Activation
NFS2-3030, NCA-2 MN Activations
Local Activation
When an MN trouble activates locally, it:
Produces a pulsed audible tone if the piezo is enabled.
Activates the panel’s trouble relay.
Flashes the TROUBLE yellow LED.
Activates Special Function Zone ZF22 (MN trouble zone).
Does not suppress Fire or any other activations.
Is acknowledged with a block acknowledgement.
Uses the TROUBLE/SCROLL DISPLAY key for scrolling.
Increments the trouble counter on the Events Code screen.
Activates “General Pending” type code at the NFS2-3030
Activates “General Trouble” and “Trouble Pending” type codes at the NFS2-3030.
Any device programmed for “Resound by Trouble” will not resound.
Displays MN TROUBLE in the upper left corner of the display, as well as other information specific to the supervisory message.
Sends an MN trouble message to the history buffer and installed printer and annunciators.
Appears as “MNT” in the Multiple Events list screen, grouped under “TROUBLE”.
Sends an MN trouble message (ZF22) out to the network.
Network Activation
NETWORK MN ACTIVE will display if all systems are normal.
Logic Zones with ZF22 (MN trouble zone) will be evaluated.
NFS2-640, NFS-320/SYS MN Activation
Local Activation
When an MN trouble activates locally, it:
Produces a pulsed audible tone if the piezo is enabled.
Activates the panel’s trouble relay.
Flashes the TROUBLE yellow LED.
Activates Special Function Zone ZF22 (MN trouble zone).
Does not suppress Fire or any other activations.
Does not activate “General Supervisory” type ID.
Any device programmed for “Resound by Trouble” will not resound.
Activates “General Trouble” or “Trouble Pending” type code.
Sends an MN Trouble message to the history buffer and installed printer and annunciators.
Sends an MN trouble message (ZF22) out to the network.
Network Activation
Logic Zones with ZF22 (MN trouble zone) will be evaluated.
NOTE: MN troubles are block acknowledged.