ID50 Series Panel - Installation, Commissioning & Configuration Manual
Configuration Mode
43
997-263-000-11, Issue 11
January 2010
3 Press the ‘
6
’ button to toggle between ‘On new zone
alarm’ and ‘On new point alarm’ input options.
4 Press ‘
4
’ to return to the Setup menu screen. All
changes will be saved on exiting.
5.5.1.7 Mains Fault Delay
By default, a mains fault is indicated within 10 seconds.
This option allows the delay to be extended up to 60
minutes in one minute increments. A fault indication
delay of more than 30 secs does not comply with
EN54 (see information at left). To configure a fault output
delay, proceed as follows:
1 From the Setup menu, using the numeric keypad press
the ‘
1
’ button to enter the Panel Options menu.The
Language screen is displayed first.
2 Press the ‘
2
/
8
’ buttons to step through the Panel
Options until the Mains Fault Delay screen is displayed.
3 Press the ‘
6
’ button to change the delay time to the
required setting:
4 Use the numeric keypad to enter the new value:
5 Press ‘
4
’ to return to the Setup menu screen. All
changes will be saved on exiting.’
5.5.1.8 Diagnostic Mode
The Diagnostic Mode option allows extended fault and
fire reporting and determines whether events are
suppressed until confirmed. To enable Diagnostic Mode:
1 From the Setup menu, using the numeric keypad press
the ‘
1
’ button to enter the Panel Options menu.The
Language screen is displayed first.
2 Press the ‘
2
/
8
’ buttons to step through the Panel
Options until the Diagnostic Mode menu is displayed.
[Setup] Un-mute = On new point alarm
> : Change ¦ : More < : Exit
6
EN54-4: 5.4
Mains fail delay
MUST not exceed 30
minutes.
1
or
8
2
6
[Setup] Mains Fault Delay = 10
> : Change ¦ : More < : Exit
[Setup] Language = English
> : Change ¦ : More < : Exit
[Setup] Mains Fault Delay = 10
Enter new value _ : Confirm < : Cancel
[Setup] Mains Fault Delay = 20
> : Change ¦ : More < : Exit
1
[Setup] Language = English
> : Change ¦ : More < : Exit