Connecting the OELD to Searchline Excel
<Figure 10. Wiring Diagram for Searchline Excel>
Green/Yellow (Safety/Protective Ground)
Red (+24 Vdc)
Black (0 Vdc)
White (420 mA Output)
0 V
+24 Vdc in
420 mA
OELD
Field
Wiring
Blue (RS485B)
Orange (RS485A)
The earth bonding arrangement must ensure that the maximum peak voltage between the unit case earth and any field cable
conductor is less than 350V. Voltages in excess of this can cause permanent damage to the units’ internal RFI protection filters.
Connecting the OELD to Searchline Excel Cross-Duct (XD)
<Figure 11. Wiring Diagram for Searchline Excel CrossDuct>
Field
Wiring
Searchline Excel
CrossDuct
Transmitter
Searchline
Excel CrossDuct
Receiver
To Heater
Reflector Panel
Blcak or Brown (+V)
Orange (RS485A)
White (0 V)
Blue (RS485B)
Green (Earth)
White (mA Output)
Black (0 Vdc)
Red (+24 Vdc)
Green/Yellow
(Safty/Protective Ground)
Red (+24 Vdc)
Black (0 Vdc)
0 V
+24 Vdc in
420 mA
Green/Yellow (Safety/Protective Ground)
OELD
The earth bonding arrangement must ensure that the maximum peak voltage between the unit case earth and any field cable
conductor is less than 350V. Voltages in excess of this can cause permanent damage to the units’ internal RFI protection filters.