SHC-1 Connection
WARNING
Do not Attempt to connect SHC1 Handheld interrogator directly to the OELD. Always use the SHC Protection Device.
Connect the SHC1 Handheld Interrogator to the OELD using the SHC Protection Device.
<Figure 14. SHC Protection Device>
Flying Lead
IS Connector
Note
A hot work permit may be required for this procedure.
Carry out the following procedure to connect using the protection device:
1. Isolate all power supplies.
2. Remove the OELD cover
3. Lift out the electronics module and locate the blue and orange terminals market ‘SHC1 485 COMM’
4. Connect the flying leads of the SHC Protection Device to the these terminals as shown:
<Figure 15. Connection for the SHC Protection Device>
SHC Protection
Device Flying Lead
Brown
Blue
5. Connect the SHC1 hand-held interrogator to the IS connector on the end of the SHC Protection Device.
6. Re-apply power.