3. PLACE A JUMPER (PIECE OF WIRE) BETWEEN Y AND W IF YOU ARE USING A HEAT PUMP WITHOUT
AUXILIARY/BACKUP HEAT. M32169A
Set Heating Fan Control
Set jumper JP1, on the back of the thermostat, if you have connected a wire to the G terminal.
HG: Leave the jumper in this factory-set position if you have a gas or oil furnace.
HE: Place the jumper to this position if you have an electric furnace.
Incorrect jumper setting: An incorrect setting is notice-able in a gas or oil heating system. When heating starts, you
will initially feel cold air coming out of the vents as the fan is running before the furnace has enough time to heat up
the air.
Set Heat Pump Reversing Valve
Set jumper JP2, on the back of the thermostat, if you have a heat pump.
O: Leave the jumper in this factory-set position if you have connected O wire to the O/B terminal.
B: Place the jumper to this position if you have connected B wire to the O/B terminal.
Incorrect jumper setting: The heat pump operation will be reversed, i.e., it will cool in Heat mode and will heat in
Cool mode.
Install Batteries and Thermostat