19 33-00131ES—01
System setup
Function Settings & Options
0500
Filter Change
Reminder
The reminder
appears after
selected number of
days run time not
actual time.
0 Off (no reminder)
1 Reminder after 10-day run time (about 1 calendar month)
2 Reminder after 30-day run time (about 3 calendar months)
3 Reminder after 60-day run time (about 6 calendar months)
4 Reminder after 90-day run time (about 9 calendar months)
5 Reminder after 120-day run time (about 1 calendar year)
6 Reminder after 180-day run time (about 18 calendar months)
7 Reminder after 270-day run time (about 2 calendar years)
8 Reminder after 365-day run time (about 3 calendar years)
9 30 calendar days
10 60 calendar days
11 90 calendar days
12 120 calendar days
13 180 calendar days
14 365 calendar days
0502
Furnace Filter for
Run Time
1 Counts both heat and cool
0 Counts cool only
0520
UV Lamp
Replacement
0 Disabled
1 365 days
2 730 days
0530
Adaptive Intelligent
Recovery
TM
See page 15 for
more information.
1 On
0 Off
0540
Program Periods
4 4 program periods (Wake, Leave, Return, Sleep)
2 2 program periods (Wake, Sleep)
0580
Compressor
Protection
5 5-minute compressor off time
[Other options: 0, 1, 2, 3 or 4-minute off time)
0600
Heat Temperature
Range Stop
90 Max. heat temperature setting is 90°F (32°C)
[Other options: 40-89°F (4°C to 32°C)]
0610
Cool temperature
range stop
50 Min. cool temperature setting is 50°F (10°C)
[Other options: 51-99°F (11°C to 37°C)]
0615
Energy Saving
Heat Setpoint
65 65°F (18.5°C)
40-90°F (4.5°C to 32°C)
0616
Energy Saving
Cooling Setpoint
78 78°F (25.5°C)
50-99°F (10°C to 37°C)
0640
Clock Format
12 12-hour clock (i.e., “3:30 pm”)
24 24-hour clock (i.e., “15:30”)
0650
Extended fan
timer (heat)
0 Off
90 Fan runs for 90 seconds after call for heat ends
[Other options: 30, 60, 120]
0660
Extended Fan
Timer (cool)
0 Off
90 Fan runs for 90 seconds after call for cooling ends
[Other options: 30, 60, 120]
What other functions can I change? (See page 16 for instructions.)