7800 SERIES S7800A KEYBOARD DISPLAY MODULE
3
65-009
0-6
BURNER CONTROL
BACK
2-3/4
(69)
3. Installer must be a trained, experienced, flame safeguard
service technician.
4. After installation is complete, check out the product oper-
ation as provided in these instructions.
5. Be sure wiring complies with all applicable codes,
ordinances and regulations.
6. See Fig. 5, 6 and 7 for S7800A unique wiring
connections.
Edit: -
+
4-27/32 (123)
ENTER
5/32
(4)
29/32
(23)
IMPORTANT
1. This equipment generates, uses and can radiate
radio frequency energy and, if not installed and used
in accordance with the instructions, can cause inter-
ference to radio communications. It has been tested
4-3/32 (104)
5/16
and found to comply with the limits for a Class B com-
1-5/16
19/32
(15)
1-1/4
(32)
7/16 (11)
1-1/32
(26)
1/2
(13)
(8)
puting device of Part 15 of FCC rules which are
designed to provided reasonable protection against
such interference when operated in a commercial
environment. Operation of this equipment in a resi-
dential area can cause interference, in which case,
15/32
(49)
2-7/16 (62)
29/32
(23)
5/32 (4)
13/
2 -1 /3 2
(52)
5/16
(8)
users, at their own expense, can be required to take
whatever measures are required to correct this inter-
ference.
2. This digital apparatus does not exceed the Class
B
limits for radio noise for digital apparatus set out in the
Radio Interference Regulations of the Canadian
Department of Communications.
(12)
3-7/8 (99)
32
(11)
M22870
Humidity
Fig. 1. Approximate dimensions of S7800A1001 in. (mm).
INSTALLATION
WARNlNG
Electrical Shock Hazard.
Can cause severe injury, death or property damage.
Disconnect the power supply before beginning
installation to prevent electrical shock and equipment
damage. More than one power supply disconnect can
be involved.
When Installing This
Product..
1. Read these instructions carefully. Failure to follow them
could damage the product or cause a hazardous condi-
tion.
2. Check the ratings given in the instructions and marked
on the product to make sure the product is suitable for
your application.
Install the S7800A where the relative humidity never reaches
the
saturation point. The S7800 is designed to operate in a
maximum 85% RH continuous, noncondensing, moisture
environment.
Vibration
Do not install the S7800A where it can be subjected to
vibration in excess of 0.5G continuous maximum vibration.
Weather
The S7800A is not designed to be weather tight. If installed
outdoors, the S7800A must be protected by an approved
weather-tight enclosure such as the 204718A or 204718C
NEMA 4 Enclosure listed in Accessories.
S7800A1001 Series 5 Embedded Features
A. See Appendix A to set up the embedded features:
SERVlCE NOTE:
The S7800A1001 can either do the Expanded Annunciator
Feature or ModBus -- not both. If BOTH are required, order
the S7810M1003 ModBus Module for the ModBus option.

Questions and Answers: