S 8 61 0U UNIVERSAL INTERM ITTEN T P H O T MODULE
Table 4. Conversion from Robertshaw SP715 and SP735C to S8610U1003 (Includes 780-XXX and USI715U).
Terminal Function
Replacement
Control
Old Control SP715 and SP735
(includes 780-XXX and USI 715U)c>d
Procedural Notes
Honeywell
S8610U1003 7000D Valve 7100D Valve 7100K Valve
Main valve operator MV MV
(to: Valve TH)
MV
(to: Valve M)
MV
(to: Valve TR)
Main valve and pilot
common
MV/PV MV/PV
(to: Valve TR)
MV/PV
(to: Valve C)
PV
(to: Valve C and TH)
Pilot valve operator PV PV
(to: Valve
PILOT)*
PV
(to: Valve P)
PV
(to: Valve PICK &
HOLD)
*This is the terminal not
jumpered to TR.
Burner ground
connection
GND
(BURNER)
GND GND GND
Transformer
secondary
(unswitched leg)
24V GND TR TR TR
24V No connection No
connection
No connection
Transfomer
secondary
(switched leg)
E3a E3a
E3a
When supplied, E3
provides connection to
Lockout Timer.
TH-W TH TH TH If LO-15 is part of the
installation, use the
wire disconnected from
E1 tagged Thermostat.
Flame sensor
SENSEb SENSEe SENSEe SENSEe
Pilot igniter SPARK IGN IGN IGN
1. Use existing wiring harness to make connections to S8610 per table. IMPORTANT: If installation includes LO-15
Lockout Timer, discard wires to E3 and TH. Disconnect and retain wire to LO-15 terminal E1. Tag wire,Thermostat.
Discard LO-15.
2. On 7000D series valve, retain (or install) white jumper between valve TR and pilot solenoid.
a If LO-15 Lockout timer is not installed, E3 connector provided on SP715 is not used.
b Important: If the USI 715U with combination igniter sensor is not used, remove black jumper quick connect from
Sense terminal of S8610U1003. Cut jumper wire at circuit board and discard.
c For replacement of Robertshaw Flame Switch systems (SP710, 720, 730, 750, 780-700, 780-701,780-710, 780-711,
780-712 and 780-713), see Honeywell Ignition Control Handbook.
d 780-715 and USI 715U are equivalent to SP715; 780-735 and 780-737 are equivalent to SP735. For other 780-XXX
models, see notec.
e OPT. SENSOR on USI 715U. No external connection if combination igniter sensor is used.
69-07293 6