S8 610 U UNIVERSAL INTERM ITTEN T PILO T M ODULE
S8610U
/ \ POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
fk ALTERNATE LIMIT CONTROLLER LOCATION.
^ MAXIMUM CABLE LENGTH 3 ft (0.9m).
/ \ CONTROLS IN 24V CIRCUIT MUST NOT BE GROUND LEG TO TRANSFORMER.
5 REMOVE PLUG ONLY IF USING VENT DAMPER. FUSE BLOWS ON STARTUP WHEN PLUG IS
REMOVED AND VENT DAMPER WIRING HARNESS IS INSTALLED, THEN MODULE OPERATES
ONLY WHEN VENT DAMPER IS CONNECTED.
/k, REMOVE JUMPER AND CONNECT SENSE TERMINAL ON TWO ROD APPLICATION ONLY.
7 IF THE VENT DAMPER IS CONNECTED, WIRE 24V TERMINAL, AS SHOWN. CONNECT VENT
DAMPER CABLE IN PLACE OF PLUG SHIPPED WITH THE S8610U. IF NO VENT DAMPER IS
CONNECTED, DO NOT WIRE 24V TERMINAL.
30 VA MINIMUM WHEN VENT DAMPER IS CONNECTED TO DAMPER PLUG. M2641
Fig. 2. S8610U in heating system with atmospheric burner.
S8610U
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
ALTERNATE LIMIT CONTROLLER LOCATION.
MAXIMUM CABLE LENGTH 3 ft (0.9m).
CONTROLS IN 24V CIRCUIT MUST NOT BE GROUND LEG TO TRANSFORMER.
LEAVE VENT DAMPER PLUG CONNECTED.
REMOVE JUMPER AND CONNECT SENSE TERMINAL ON TWO ROD APPLICATION ONLY. M2642B
Fig. 3. S8610U in heating system with power-assisted combustion.
9
69-07293