S 8 61 0U UNIVERSAL INTERM ITTEN T P H O T MODULE
Table 6. Conversion from Camstat, Fenwal or HSC to S8610U1003.
Terminal
Function
Replacement
Control Old Control
Procedural Notes
Honeywell
S8610U1003
CAMSTAT
IPI-24-00a
FENWAL
05-20Xb
HSC 1003-3
and 1003-3003
M a in v a lv e
o p e ra tor
M V M V M A IN V A L V E M V
—
M a in v a lv e a nd
pilo t c o m m on
M V /P V G N D G R O U N D G N D /C O M F e nw al o nly: run s e p a ra te
lea d to S 86 1 0 va lve
co m m o n te rm ina l.
P ilot v a lv e
o p e ra tor
PV PV P IL O T V A L V E PV
—
B u rn e r g ro u n d
co n n e c tio n
G N D
(B U R N ER )
G N D T o a s s u re g o o d g ro un d, run
se p a ra te w ire fro m p ilo t
b u rn e r to S 86 1 0 G N D
(B U R N E R ).
T ra n s fo rm er
s e c o n d a ry
(u n s w itc h e d leg)
2 4 V G N D T2 G R O U N D G N D /C O M
2 4 V No c o n n e c tio n No co n n e c tio n No c o n n e ctio n
—
T ra n s fo rm er
s e c o n d a ry
(s w itc he d leg)
T H -W T1 P O W ER 2 4 V A C
F la m e s e n so r S E N SE
Sc
—
S E N S O R c
—
P ilot ig n ite r S P A R K IG N H.V. IG N C O IL S trip m o d u le e n d o f ig n itio n
ca b le a s n e c e s s a ry a nd
a tta c h in s u la te d q u ic k
co n n e c t fo r c o n n e ctio n to
S 861 0 .
a U se e x istin g w irin g harne ss to m ake co n n e ctio n s to S 8610.
b T ag all w ires at m od u le c o n n e c to r w ith te rm inal d e sig nations. C u t w ires a t c o n necto r, a tta ch q u ic k c o nn ects a nd
co n n e ct to S 861 0; pe r table.
c I m p o r t a n t : Remove black jumper quick connect from Sense terminal of S8610U1003; cut jumper wire at circuit board
and discard.
69-0729—3 8