S8600B,C,H,M; S8610B,C,H,M; S8670D,E,J,K INTERMITTENT PILOT GAS IGNITION CONTROL
 
บริษัท เอดีดี เฟอร์เนส จํากัด 
ADD FURNACE CO.,LTD. 
44 ซอยบรมราชชนนี 70 ถนนบรมราชชนนี แขวงศาลาธรรมสพน์ เขตทวีวัฒนา กรุงเทพฯ 10170 
โทร: 02-888-3472 โทร: ออกแบบ:08-08-170-170 แฟกซ์: 02-888-3258 
https://www.add-furnace.com E-mail: sales@add-furnace.com 
 
 
 
— 
Operating ambient temperatures between -40°F and 175°F (-
40°C and 79°C); (165°F  [74°C] for S8610 and
 
S8670 models).
 
— 
Relative humidity below 95% noncondensing.
 
— 
Protection from water, steam or corrosive chemicals that are 
used to clean the appliance.
 
— 
Protection from dripping water, such as from an 
overfilled humidifier or from condensation.
 
— 
Protection from dust or grease accumulation.
 
 
Mount the Ignition Module 
Select a location close enough to the burner to allow a short (3 ft. 
[0.9 m] max.), direct cable route to the pilot burner. Ambient 
temperature at the module must be within the range listed under 
Operating Temperature, on page 2. The module must be protected 
from water, moisture, corrosive chemicals and excessive dust and 
grease.
 
Mount the module  with the terminals down  to protect  them  from 
dripping water and dust. As an alternative, it can also be mounted 
with the terminals on either side.
 
 
IMPORTANT
 
Do not mount with terminals facing up.
 
 
M29897
 
 
Fig. 1. Incorrect Mounting (Model S8600M shown).
 
 
Fasten securely with four No. 6-32 machine or No. 8 sheet metal 
screws.
 
 
Mount the System Controls 
Mount any required controls, such as the gas control, spark 
igniter, flame sensor, thermostat, limit, and transformer according 
to manufacturer’s instructions.
 
 
Wire the System 
 
 CAUTION 
Equipment Damage Hazard.
 
Disconnect  power  supply  before  beginning  wiring  or 
making wiring connections to prevent electrical shock or 
equipment damage.
 
 
All wiring must comply with local codes and ordinances. See Fig. 2 
and Table 4 for proper wiring connections.
 
IMPORTANT
 
1. 
As shown in the wiring diagrams, a common ground 
is required on:
 
aThe pilot burner mounting bracket, and bThe 
GND(BURNER) terminal on the ignition
 
module. Failure to use the GND(BURNER) terminal 
may result in intermittent loss of spark and/or loss of 
flame current sensitivity.
 
2. 
Make sure the transformer has adequate VA. The 
ignition module requires at least 0.1 A at 24 Vac. Add the 
current draws of all other devices in the control circuit, 
including the pilot and main valves in the gas control, 
and multiply by 24 to determine the total VA requirement 
of these components. Add this total to 2.4 VA (for the igni- 
tion module). The result is the minimum trans- former VA 
rating. Use a Class II transformer if replacement is 
required.
 
 
CONNECT IGNITION CABLE
 
Use Honeywell ignition cable or construct an ignition cable that 
conforms to suitable national standards such as Underwriters 
Laboratories Inc. See Table 2 and Table 3.
 
.
 
Table 2. Honeywell Pre-assembled Ignition Cables (UL 
Style 3257).
 
 
1/4 inch quick 
connect, 
insulated
 
Rajah connector 
receptacle, 90 degree 
rubber boot
 
1/4 inch quick 
connect, 
insulated
 
Rajah connector 
receptacle, straight 
rubber boot
 
 
Table 3. Recommended Ignition Cable for Field 
Assembly.
 
 
Cable must be no longer than 36 in. (0.9 m). Solid conductor cable 
recommended. To construct a cable, fit one end of ignition cable with 
1/4 in. diameter Rajah connector receptacle and the other with a 1/4 
in. female quick connect. Protect both ends with insulated boots.
 
NOTE:  The cable must not run in continuous contact with a metal 
surface or spark voltage will be greatly reduced. Use 
ceramic or plastic standoff insulators as required. 
Resistive spark cable reduces spark voltage and may 
impact appliance performance.
 
To install:
 
 
(1) 
Connect one end of the cable to the male quick 
connect SPARK terminal on the igni- tion module.
 
(2) 
Connect the other end of the cable to the igniter 
or igniter-sensor stud on the pilot burner/igniter-
sensor.
 
 
CONNECT IGNITION MODULE
 
 
NOTE: Refer to Fig. 2 and Table 4 for the location of each 
connection.