EasyManua.ls Logo

Honeywell S9201A1010 - User Manual

Honeywell S9201A1010
6 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
Loading...
S9201A1010 INTEGRATED FURNACE CONTROL
APPLICATION
The S9201A1010 Integrated Furnace Control is used in
high efficiency gas fired warm air furnaces with an induced
draft blower and a combination hot surface igniter/flame
sensor. The S9201 provides:
sequencing of ignition and burner operation,
up to 5 trials for ignition before lockout, if initial lightoff
is unsuccessful,
ignition return if established flame fails during the run
cycle.
control of indoor blower motor operation, including
heating and cooling speeds,
control of the induced draft blower motor,
control of the humidifier, and
control of the electronic air cleaner.
The S9201 cannot be used with a vent damper.
The S9201 Integrated Furnace Control is intended for
residential furnaces only. Other applications require Hon-
eywell Residential Design Engineering review and written
approval. Contact your Honeywell Sales Representative for
assistance.
VOLTAGE: 24 Vac.
CURRENT DRAW: Inrush—0.32 A plus gas control current;
running—0.10 A plus gas control current.
POWER CONSUMPTION: Inrush—7.7 VA plus gas control
VA; running—2.4 VA plus gas control VA.
THERMOSTAT ANTICIPATOR SETTING: 0.10 A plus gas
control load. For VR8204 and VR8205, set anticipator to
0.6 A.
PREPURGE TIMING: 30 sec., nominal.
WARM UP TIMING: 36 sec.
TRIAL FOR IGNITION: 9 sec., nominal. Igniter is off 1 sec.
before end of ignition trial.
FLAME FAILURE RESPONSE TIME: 2.3 sec. max. with 5
µA flame signal.
FLAME CURRENT: 0.8 µA DC, min.
IGNITION TRIALS: Five, with 30 sec. purge between trials.
INDOOR FAN ON DELAY: 30 sec., fixed.
INDOOR FAN OFF DELAY: 90 sec., factory set; selectable
to 45, 60 or 75 sec.
GAS CONTROL: Any 24 Vac redundant gas control rated at
1 A or less. Honeywell VR8204 or VR8205 recommended.
COOLING CONTACTOR: Any 24 Vac contactor rated at 1 A
or less.
HOT SURFACE IGNITER: Norton Model 201 or equivalent.
NOTE: Igniter must meet the following minimum specifica-
tions throughout its life:
Igniter must reach 1000° C [1832° F] within 36 seconds
with 102 Vac applied.
Igniter must maintain at least 500M ohms insulation
resistance between the igniter leadwires and the ig-
niter mounting bracket.
Igniter must not develop an insulating layer on its
surface (over time) which would prevent flame sensing.
Igniter surface area immersed in flame must not ex-
ceed 1/4 of the grounded area immersed in flame. This
would prevent flame sensing.
Igniter current draw at 132 Vac must not exceed 5 A.
2. Check the ratings given in these instructions to make
sure the integrated furnace control is suitable for your appli-
cation.
3. Installer must be a trained, experienced service techni-
cian.
4. After installation is complete, check out operation as
provided in these instructions.
WARNING
FIRE OR EXPLOSION HAZARD.
MAY CAUSE PROPERTY DAMAGE, SEVERE
INJURY OR DEATH.
1. The integrated furnace control can malfunction
if it gets wet, leading to accumulation of explo-
sive gas.
Never install where water can flood, drip
or condense on control.
Never try to use an integrated furnace
control that has been wet—replace it.
2. Liquefied petroleum (LP) gas is heavier than air
and will not vent upward naturally.
Do not operate electric switches, lights,
or appliances until you are sure the ap-
pliance area is free of gas.
CAUTION
1. Disconnect power supply before beginning wiring
to prevent electrical shock or equipment damage.
2. If furnace control must be mounted near moisture or
water, provide suitable waterproof enclosure.
LOCATION
The integrated furnace control is mounted inside the
furnace wiring compartment. The location must provide:
Access to the field wiring terminals.
Operating ambient temperature between minus 40°
F and plus 150° F [minus 40° C and plus 66° C], except
temperatures to 170° F [77° C] are acceptable for
occasional brief periods.
Relative humidity below 95% non-condensing.
Protection from water, steam or corrosive chemicals
that might be used to clean the appliance.
Protection from dripping water, such as from an over-
filled humidifier or from condensation.
Protection from dust or grease accumulation.
A barrier between line and low voltage field wiring
terminals.
MOUNTING
Select a location close enough to the burner to allow a
short, direct cable route to the igniter. The integrated furnace
control can be mounted in any position. Line voltage wiring
terminals must be in an enclosure separate from low voltage
field wiring terminals. The unit is designed to snap in to
predrilled holes in the mounting surface.
INSTALLATION
WHEN INSTALLING THIS PRODUCT…
1. Read these instructions carefully. Failure to follow them
could damage the product or cause a hazardous condition.
G.G. Form Number 69-0685
9-91 ©Honeywell Inc. 1991
Question and Answer IconNeed help?

Do you have a question about the Honeywell S9201A1010 and is the answer not in the manual?

Summary

Application Overview

Installation Instructions and Safety

General Installation Guidelines

Follow careful instructions, check ratings, ensure trained installer, and verify operation after installation.

Safety Warnings and Precautions

Includes fire/explosion hazards from water exposure and LP gas, plus electrical shock and equipment damage cautions.

Location and Mounting Requirements

Mount control inside furnace wiring compartment with access, appropriate temperature/humidity, and protection.

Wiring Connections and Diagrams

Wiring Cautions and Important Notes

Check diagrams, disconnect power, follow codes, ensure adequate transformer VA, and use correct wiring practices.

Terminal Connections Table

Details factory and field wiring connections for S9201 to various components like igniter, blower, and thermostat.

Typical Wiring Diagram

Illustrates typical wiring connections for the S9201 integrated furnace control with associated components.

Settings and Adjustments

Thermostat Anticipator Setting

Instructions for setting the heat anticipator in the thermostat based on gas control current draw.

Indoor Fan Off Delay Adjustment

Details on how to adjust the fan off delay time using switches, with a table of settings.

System Checkout Procedures

Normal Operation Checkout

Steps to verify normal heating cycle operation by checking system sequence with thermostat calls.

Safety Shutoff Operation Checkout

Procedure to test safety shutoff by simulating flame failure and verifying lockout sequence.

Troubleshooting Guide and Status Lights

Troubleshooting Warnings and Important Notes

Includes hazards, do not modify device, check manufacturer instructions, static discharge precautions, and repair limitations.

Status Lights Interpretation

Explanation of PWR and OK status lights on the control for indicating input power and internal checks.

Troubleshooting Guide Flowchart

Troubleshooting Flowchart Steps

Step-by-step guide with checks for induced draft motor, igniter, gas control, and blower motor issues.

Overview

The Honeywell S9201A1010 Integrated Furnace Control is a device designed for use in high-efficiency gas-fired warm air furnaces equipped with an induced draft blower and a combination hot surface igniter/flame sensor. Its primary function is to manage the sequencing of ignition and burner operation, ensuring safe and efficient heating.

One of the key usage features of this control is its ability to handle multiple ignition attempts. If the initial lightoff is unsuccessful, the S9201 will attempt ignition up to five times before initiating a lockout. This feature enhances reliability by providing several chances for the furnace to ignite properly. Furthermore, the control is designed to return to ignition if an established flame fails during the run cycle, ensuring continuous heating operation when possible.

Beyond ignition, the S9201A1010 also manages the operation of various furnace components. It controls the indoor blower motor, offering both heating and cooling speeds to suit different comfort needs. The induced draft blower motor is also under its command, crucial for proper venting and combustion. Additionally, the control integrates with other home comfort systems, managing the operation of both the humidifier and the electronic air cleaner, contributing to overall indoor air quality and comfort.

For safety and proper operation, it's important to note certain usage limitations. The S9201A1010 cannot be used with a vent damper. It is specifically intended for residential furnaces, and any other applications require prior review and written approval from Honeywell Residential Design Engineering. This ensures that the control is used in environments for which it has been designed and tested, preventing potential hazards or malfunctions.

Maintenance and troubleshooting are facilitated by several features. The control includes two status lights: "PWR" and "OK." The "PWR" light illuminates whenever the control receives 24 Vac input power from the system transformer, indicating that the device is powered. The "OK" light signals that the control's internal checks are satisfactory. This light pulses at approximately six-second intervals during normal operation, confirming that the continuous self-check is functioning correctly. If the "OK" light goes out during operation, it indicates an internal issue, and the control must be replaced.

When troubleshooting, it's crucial to follow specific procedures. All meter readings should be taken within the trial for ignition period. Once this period ends, the system must be reset by setting the thermostat to its lowest setting and waiting at least 45 seconds before proceeding. This ensures accurate readings and prevents misdiagnosis. If any component is found not to be functioning properly, it's essential to verify its correct installation and wiring before considering replacement.

A critical maintenance consideration is the susceptibility of the integrated furnace control to static discharge. Static electricity can damage the device, so it's recommended to touch a metal surface to discharge any static electricity before handling the furnace control. This preventative measure helps protect the sensitive electronic components within the control.

The S9201A1010 is not designed to be repaired. If troubleshooting indicates a malfunction, the integrated furnace control must be replaced. This approach ensures that any faulty unit is swapped out for a new, fully functional one, maintaining the safety and reliability of the furnace system. Only trained and experienced service technicians should service these integrated furnace control systems, following the checkout steps and troubleshooting guide provided in the manual to ensure the system operates normally after any intervention.

Installation guidelines emphasize proper placement and wiring. The control should be mounted inside the furnace wiring compartment in a location that allows access to field wiring terminals. The operating ambient temperature range is specified, along with requirements for relative humidity and protection from water, steam, corrosive chemicals, dripping water (e.g., from an overfilled humidifier), dust, and grease accumulation. A barrier between line and low voltage field wiring terminals is also necessary. The unit is designed for easy installation, snapping into predrilled holes on the mounting surface. Selecting a location close to the burner is recommended to allow a short, direct cable route to the igniter.

In summary, the Honeywell S9201A1010 Integrated Furnace Control is a comprehensive solution for managing residential gas furnaces, offering reliable ignition sequencing, blower motor control, and integration with other comfort systems, all while incorporating features for easy troubleshooting and emphasizing safety and proper installation practices.

Honeywell S9201A1010 Specifications

General IconGeneral
Ignition TypeIntermittent Pilot
Frequency60 Hz
Housing MaterialPlastic
Trial for Ignition4 seconds
Ignition SourceSpark
MountingPanel
Weight1.5 lbs

Related product manuals